Deutz EMR4 controller, memory, supply and immobilizer fault codes

Faults of the controller itself and what it runs on. Internal faults, memory and dataset errors, manipulation monitoring and the immobilizer, the afterrun after key off, a further controller 3, the 5 V sensor supplies and the battery voltage (SPN 168), plus ECU temperature (SPN 1136).

More about these parts

A supply fault shows up on several sensors at once.

FaultCheckSPN 168FMI 4Deutz · Machine - Battery voltage
Plug the service tool in hereDiagnosticport, 9-pin

Where to read it

Read the active and stored faults with Deutz SerDia (or the machine maker's diagnostic tool) on the engine diagnostic plug.

What do these codes mean?

Deutz codes SPN 168 FMI 0 to SPN 524278 FMI 11 are all about the eMR4 controller, memory, supply and immobilizer. The most common failure type is part or controller (9 of 25); 4 need an immediate stop. Start with this check: measure battery voltage with the key on, cranking and running, and check the terminals and ground strap.

How urgent are they?

4 of 25 codes here mean stop now; the other 21 can wait until the shift ends, but find the cause before the next one.

  • Stop now4
  • Check soon21

What should I check first?

Measure battery voltage with the key on, cranking and running, and check the terminals and ground strap

Shared checks

25 of 25

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Machine - Battery voltage5 codes

    • Deutz SPN 168 FMI 0Machine - Battery voltage: Reading too high· most severe

      The EMR4 measures the machine battery voltage (at the EMR4 supply connector, fed from the machine battery and ignition) above its operating range; the system voltage is above the allowed window.· Real condition
      Check soon

      Causes

      • Overvoltage points at the alternator regulator or a jump-start with the wrong supply
      • Regulator fault in the alternator

      Checks

      1. 1Measure battery voltage at the terminals with the engine off and running
      2. 2Check the voltage at the EMR4 supply connector against the battery voltage; a drop shows a bad connection
      3. 3Check the main ground between engine block, frame and battery negative
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Machine - Battery voltage - Data above normal operational range (Most severe level)

    • Deutz SPN 168 FMI 1Machine - Battery voltage: Reading too low· most severe

      The EMR4 measures the machine battery voltage (at the EMR4 supply connector, fed from the machine battery and ignition) below its operating range; the system voltage is below the allowed window.· Real condition
      Check soon

      Causes

      • Undervoltage points at a weak battery, high resistance in a power feed, or the alternator not charging
      • Alternator not charging

      Checks

      1. 1Measure battery voltage at the terminals with the engine off and running
      2. 2Check the voltage at the EMR4 supply connector against the battery voltage; a drop shows a bad connection
      3. 3Check the main ground between engine block, frame and battery negative
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Machine - Battery voltage - Data below normal operational range (Most severe level)

    • Deutz SPN 168 FMI 2Machine - Battery voltage: Erratic reading

      The EMR4 measures the machine battery voltage (at the EMR4 supply connector, fed from the machine battery and ignition) erratic or implausible; the system voltage is jumping or disagrees with expectation.· Erratic or implausible
      Check soon

      Causes

      • Corroded battery terminal or ground strap
      • Loose battery or ground connection
      • Alternator ripple from a failing diode

      Checks

      1. 1Check the main ground between engine block, frame and battery negative for corrosion and loose lugs
      2. 2Measure battery voltage at rest and with the engine running; a 12 V system should charge around 13.5 to 14.5 V, a 24 V system about twice that
      3. 3Check the main ground between engine block, frame and battery negative
      4. 4Measure battery voltage at the terminals with the engine off and running
      5. 5Check the voltage at the EMR4 supply connector against the battery voltage; a drop shows a bad connection
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Machine - Battery voltage - Data erratic intermittent or incorrect

    • Deutz SPN 168 FMI 3Machine - Battery voltage: Voltage high / shorted high

      The EMR4 measures the machine battery voltage (at the EMR4 supply connector, fed from the machine battery and ignition) above range or shorted to supply; the voltage at the EMR4 supply pin is too high.· Shorted high
      Check soon

      Causes

      • Overvoltage points at the alternator regulator or a jump-start with the wrong supply
      • Alternator regulator failing and over- or undercharging
      • Wrong voltage battery or booster supply

      Checks

      1. 1Check the main ground between engine block, frame and battery negative for corrosion and loose lugs
      2. 2Measure battery voltage at the terminals with the engine off and running
      3. 3Check the main ground between engine block, frame and battery negative
      4. 4Check the voltage at the EMR4 supply connector against the battery voltage; a drop shows a bad connection
      5. 5Measure battery voltage at rest and with the engine running; a 12 V system should charge around 13.5 to 14.5 V, a 24 V system about twice that
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

      Good: Open circuit (OL) between them. Any low reading is the short.

      Source wording:Machine - Battery voltage - Voltage above normal or shorted to high source

    • Deutz SPN 168 FMI 4Machine - Battery voltage: Voltage low / shorted low

      The EMR4 measures the machine battery voltage (at the EMR4 supply connector, fed from the machine battery and ignition) below range or shorted to ground; the voltage at the EMR4 supply pin is too low.· Shorted low
      Check soon

      Causes

      • Alternator regulator failing and over- or undercharging
      • Corroded battery terminal or ground strap
      • High-resistance connection in the ignition or power feed to the EMR4
      • Undervoltage points at a weak battery, high resistance in a power feed, or the alternator not charging

      Checks

      1. 1Check the main ground between engine block, frame and battery negative
      2. 2Check the voltage at the EMR4 supply connector against the battery voltage; a drop shows a bad connection
      3. 3Measure battery voltage at the terminals with the engine off and running
      4. 4Check the main ground between engine block, frame and battery negative for corrosion and loose lugs
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Machine - Battery voltage - Voltage below normal or shorted to low source

      Full page for SPN 168 FMI 4
  • Engine - ECU calibration memory1 code

    • Deutz SPN 630 FMI 12Engine - ECU calibration memory: Bad device or component

      The EMR4 cannot read its calibration memory correctly.· Part or controller
      Stop now

      Causes

      • Corrupt calibration data after a failed programming or power loss
      • Failed memory inside the EMR4
      • Supply interruption while writing data
      • Wrong data set loaded

      Checks

      1. 1Read the data set version in SerDia and compare it with the engine data plate
      2. 2Check battery supply stability during any programming, since a power dip corrupts the data
      3. 3Reflash the correct data set if your dealer can supply it for this engine
      4. 4Replace the EMR4 if the memory test keeps failing after a reflash
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Engine - ECU calibration memory - Bad intelligent device or component

  • Engine - Sensor supply voltage1 code

    • Deutz SPN 1079 FMI 13Engine - Sensor supply voltage: Out of calibration

      The EMR4 sees the sensor supply voltage 1 (5 V reference) (from the EMR4 to the engine sensors) outside its calibrated window.· Part or controller
      Check soon

      Causes

      • Water in a connector shared by the sensors on the line
      • Harness chafe shorting the 5 V line to ground or to another wire
      • A fault inside the EMR4 supply stage

      Checks

      1. 1Measure the 5 V supply at the sensor connectors with the key on
      2. 2Measure the 5 V supply at the EMR4 pin and at one of the sensor connectors and compare
      3. 3Unplug sensors on that 5 V circuit one by one while watching the supply; the one that brings it back is the culprit
      4. 4Read all active codes in SerDia; sensors on the same supply fail together
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Engine - Sensor supply voltage 21 code

    • Deutz SPN 1080 FMI 13Engine - Sensor supply voltage 2: Out of calibration

      The EMR4 sees the sensor supply voltage 2 (5 V reference) (from the EMR4 to a second group of engine sensors) outside its calibrated window.· Part or controller
      Check soon

      Causes

      • Water in a connector shared by the sensors on the line
      • A fault inside the EMR4 supply stage
      • Harness damage near the engine connector

      Checks

      1. 1Unplug each sensor on the group in turn and note which one restores the 5 V reference
      2. 2Read all active codes in SerDia; sensors on the same supply fail together
      3. 3Check the harness section where both 5 V groups run together for crushed or chafed spots
      4. 4Measure the 5 V supply at the EMR4 pin and at one of the sensor connectors and compare
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Engine - ECU temperature1 code

    • Deutz SPN 1136 FMI 0Engine - ECU temperature: Reading too high· most severe

      The EMR4 reports its own internal temperature above range.· Real condition
      Check soon

      Causes

      • Controller mounted where heat soaks in, such as next to the exhaust
      • Missing heat shield or blocked airflow around the ECU
      • Very high engine bay temperature from a failed cooling fan
      • Internal sensor drift

      Checks

      1. 1Check the ambient temperature around the ECU and its mounting
      2. 2Check that heat shields are fitted and that nothing blocks airflow
      3. 3Check the cooling system and fan for overheating
      4. 4Compare with a second temperature reading in SerDia
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Engine - ECU temperature - Data above normal operational range (Most severe level)

  • Engine - Manipulation monitoring2 codes

    • Deutz SPN 523008 FMI 1Engine - Manipulation monitoring: Reading too low· most severe

      The EMR4 reports manipulation monitoring below normal.· Real condition
      Check soon

      Causes

      • Non-standard components fitted
      • Wiring changed or tampered with
      • Corrupted data set

      Checks

      1. 1Check for non-original parts, tuning boxes or changed wiring on the engine
      2. 2Read freeze frames in SerDia for the values at the time of the entry
      3. 3Compare the data set number in SerDia with the engine plate
      4. 4Contact Deutz with the data set number if the engine is unmodified
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Engine - Manipulation monitoring - Data below normal operational range (Most severe level)

    • Deutz SPN 523008 FMI 2Engine - Manipulation monitoring: Erratic reading

      The EMR4 sees the manipulation monitoring (in the EMR4 protection logic) erratic, intermittent or implausible.· Erratic or implausible
      Check soon

      Causes

      • Intermittent contact in a connector or a pin with fretting
      • Harness chafed where it moves with vibration

      Checks

      1. 1Watch the manipulation monitoring value in SerDia while wiggling the harness and connector and note when it jumps
      2. 2Compare it with a related value, since a lone odd reading points at the circuit or part itself
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Engine - Manipulation monitoring - Data erratic intermittent or incorrect

  • Engine - Immobilizer1 code

    • Deutz SPN 523330 FMI 14Engine - Immobilizer: Special instructions

      The EMR4 flags the immobilizer as special instructions.· Other
      Check soon

      Causes

      • Wrong or unlearned key or code
      • Immobilizer module fault
      • Lost or damaged CAN link to the immobilizer

      Checks

      1. 1Use the immobilizer procedure given for your machine to teach or release the key
      2. 2Check the immobilizer module supply and ground voltage at its connector
      3. 3Check the CAN link between the immobilizer and the EMR4 for open or shorted wiring
      4. 4Contact the machine maker for a code reset if the key was replaced or the ECU changed
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Engine - ECU Sensor supply voltage 31 code

    • Deutz SPN 523601 FMI 13Engine - ECU Sensor supply voltage 3: Out of calibration

      The EMR4 sees the ECU sensor supply voltage 3 (5 V reference) (from the EMR4 to a third group of sensors) outside its calibrated window.· Part or controller
      Check soon

      Causes

      • Moisture in a connector shared by sensors on this line
      • A sensor on supply 3 shorted internally
      • Water in a connector shared by the sensors on the line

      Checks

      1. 1Check the connector pins for moisture and corrosion
      2. 2Measure the 5 V supply at the EMR4 pin and at one of the sensor connectors and compare
      3. 3Read all active codes in SerDia; sensors on the same supply fail together
      4. 4Disconnect each sensor on supply 3 one at a time and recheck the reference voltage
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Engine - ECU4 codes

    • Deutz SPN 523612 FMI 3Engine - ECU: Voltage high / shorted high

      The EMR4 reports its own internal supply or output stage above range.· Shorted high
      Stop now

      Causes

      • Overvoltage on the supply from a faulty regulator
      • Internal failure of the EMR4 power stage
      • Short to supply on a sensor feed damaging the controller
      • Poor ground on the ECU housing

      Checks

      1. 1Measure battery voltage at the EMR4 connector with the engine running; excessive values point to the alternator regulator
      2. 2Check all grounds at the ECU and at the engine block
      3. 3Read all other active codes in SerDia, as a bad sensor supply can trigger this one
      4. 4If supply is clean, replace the EMR4 as a last step with a Deutz dealer
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

      Good: Open circuit (OL) between them. Any low reading is the short.

      Source wording:Engine - ECU - Voltage above normal or shorted to high source

    • Deutz SPN 523612 FMI 4Engine - ECU: Voltage low / shorted low

      The EMR4 reports its own internal supply or output stage below range.· Shorted low
      Stop now

      Causes

      • Weak battery or a bad supply cable
      • Corroded ECU connector pin on the supply
      • Internal failure of the EMR4 power stage
      • High resistance in the ignition feed

      Checks

      1. 1Measure supply voltage at the EMR4 connector while cranking; a drop below the minimum resets the controller
      2. 2Check the ECU supply and ground pins for corrosion and a loose crimp
      3. 3Load-test the battery, since a tired battery sags during cranking and resets the ECU
      4. 4If supply stays clean and the fault returns, have the Deutz dealer check the EMR4
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Engine - ECU - Voltage below normal or shorted to low source

    • Deutz SPN 523612 FMI 12Engine - ECU: Bad device or component

      The EMR4 reports itself as a bad intelligent device.· Part or controller
      Stop now

      Causes

      • Internal hardware failure in the EMR4
      • Voltage spike from a jump-start or alternator fault
      • Water ingress into the ECU housing
      • Failed flash or software

      Checks

      1. 1Check the ECU connector and housing for water and corrosion
      2. 2Measure supply voltage for spikes with the engine running
      3. 3Check whether the code returns after a full key cycle
      4. 4Replace or reflash the EMR4 only after the Deutz dealer confirms
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Engine - ECU - Bad intelligent device or component

      Full page for SPN 523612 FMI 12
    • Deutz SPN 523612 FMI 14Engine - ECU: Special instructions

      The EMR4 flags a special instruction case on its own hardware.· Other
      Check soon

      Causes

      • Controller internal condition logged for service
      • Supply interruption during shutdown
      • Software state mismatch after programming
      • Previous ECU after-run not completed

      Checks

      1. 1Read the freeze frame data in SerDia for the conditions at the time the entry was logged
      2. 2Check the key-off sequence: the EMR4 needs a few seconds after key off to complete its after-run before the supply is cut
      3. 3Check battery voltage for dips and check that the main relay or battery switch is not cutting power too early
      4. 4Re-flash the data set or contact a Deutz dealer if the entry returns after a normal key cycle
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Engine - Engine controller 33 codes

    • Deutz SPN 523704 FMI 12Engine - Engine controller 3: Bad device or component

      The EMR4 judges the engine controller 3 (exchanged between engine controllers) to be a bad device.· Part or controller
      Check soon

      Causes

      • Internal failure of the part or its electronics
      • Water, soot or dirt inside the part

      Checks

      1. 1Read the engine controller 3 status in SerDia and run any available actuator or component test
      2. 2Check supply voltage and ground at the connector with the key on to confirm it is powered
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Engine - Engine controller 3 - Bad intelligent device or component

    • Deutz SPN 523935 FMI 12Engine - Engine controller 3: Bad device or component

      The EMR4 judges the engine controller 3 (exchanged between engine controllers) to be a bad device.· Part or controller
      Check soon

      Causes

      • Internal failure of the part or its electronics
      • Water, soot or dirt inside the part

      Checks

      1. 1Read the engine controller 3 status in SerDia and run any available actuator or component test
      2. 2Check supply voltage and ground at the connector with the key on to confirm it is powered
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Engine - Engine controller 3 - Bad intelligent device or component

    • Deutz SPN 523936 FMI 12Engine - Engine controller 3: Bad device or component

      The EMR4 judges the engine controller 3 (exchanged between engine controllers) to be a bad device.· Part or controller
      Check soon

      Causes

      • Internal failure of the part or its electronics
      • Water, soot or dirt inside the part

      Checks

      1. 1Read the engine controller 3 status in SerDia and run any available actuator or component test
      2. 2Check supply voltage and ground at the connector with the key on to confirm it is powered
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Engine - Engine controller 3 - Bad intelligent device or component

  • Engine - Dataset Main and Secondary ECU not identical1 code

    • Deutz SPN 524052 FMI 11Engine - Dataset Main and Secondary ECU not identical: Root cause not known

      The EMR4 logged a fault on the dataset Main and Secondary ECU not identical (in the EMR4 and, on twin-controller engines, the Secondary ECU) but could not pin down the cause.· Other
      Check soon

      Causes

      • Intermittent wiring fault that has not stayed long enough to be classified
      • Failing part or a real condition the controller flagged

      Checks

      1. 1Read the full SerDia fault list; this code often appears next to a clearer one
      2. 2Inspect the connector and harness for chafed insulation, bent pins and moisture
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Engine - ECU Main Secondary identical1 code

    • Deutz SPN 524068 FMI 2Engine - ECU Main Secondary identical: Erratic reading

      The EMR4 sees the ECU Main Secondary identical (in the EMR4 and, on twin-controller engines, the Secondary ECU) erratic, intermittent or implausible.· Erratic or implausible
      Check soon

      Causes

      • Intermittent contact in a connector or a pin with fretting
      • Harness chafed where it moves with vibration

      Checks

      1. 1Watch the ECU Main Secondary identical value in SerDia while wiggling the harness and connector and note when it jumps
      2. 2Compare it with a related value, since a lone odd reading points at the circuit or part itself
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Engine - ECU Main Secondary identical - Data erratic intermittent or incorrect

  • Engine - ECU EEPROM error Secondary1 code

    • Deutz SPN 524233 FMI 11Engine - ECU EEPROM error Secondary: Root cause not known

      The EMR4 logged a fault on the ECU EEPROM error Secondary (in the EMR4 and, on twin-controller engines, the Secondary ECU) but could not pin down the cause.· Part or controller
      Check soon

      Causes

      • Intermittent wiring fault that has not stayed long enough to be classified
      • Failing part or a real condition the controller flagged

      Checks

      1. 1Read the full SerDia fault list; this code often appears next to a clearer one
      2. 2Inspect the connector and harness for chafed insulation, bent pins and moisture
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Engine - ECU afterun too often not waited1 code

    • Deutz SPN 524277 FMI 11Engine - ECU afterun too often not waited: Root cause not known

      The EMR4 logged a fault on the ECU afterun too often not waited (the controller keeps powered for a short time after key off to store data) but could not pin down the cause.· Other
      Check soon

      Causes

      • Intermittent wiring fault that has not stayed long enough to be classified
      • Failing part or a real condition the controller flagged

      Checks

      1. 1Read the full SerDia fault list; this code often appears next to a clearer one
      2. 2Inspect the connector and harness for chafed insulation, bent pins and moisture
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Engine - ECU afterun too often consecutive not waited1 code

    • Deutz SPN 524278 FMI 11Engine - ECU afterun too often consecutive not waited: Root cause not known

      The EMR4 logged a fault on the ECU afterun too often consecutive not waited (the controller keeps powered for a short time after key off to store data) but could not pin down the cause.· Other
      Check soon

      Causes

      • Intermittent wiring fault that has not stayed long enough to be classified
      • Failing part or a real condition the controller flagged

      Checks

      1. 1Read the full SerDia fault list; this code often appears next to a clearer one
      2. 2Inspect the connector and harness for chafed insulation, bent pins and moisture
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

Shared checks

Checks, in order

  1. 1Measure battery voltage with the key on, cranking and running, and check the terminals and ground strap
  2. 2If several sensor codes appear together, unplug sensors one at a time to find the one that loads the 5 V supply
  3. 3Read the dataset and software versions in SerDia and compare them with the engine
  4. 4Check the immobilizer or key status in SerDia
  5. 5If the code returns with supply and wiring proven good, have the dealer check the EMR4

Causes

  • Low or unstable battery voltage, a poor ground or a loose battery terminal
  • Sensor supply shorted by one failed sensor, pulling the 5 V line down
  • Dataset not matching the software after a controller swap
  • ECU overheated by a hot engine bay

Most common here: part or controller (9 of 25)

Check power and ground at the module connector with the key on, then its fuses.

When to stop

You'll notice: A warning lamp or limited function.

Let the engine cool before opening the cooling system; a hot cap releases scalding coolant. Running on with an overheat warning risks a head gasket or seized engine.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.