Deutz DPF differential pressure, DPF and DOC temperature, and DPF load fault codes

The sensors and calculations behind the diesel particulate filter: the differential pressure sensor across the filter (SPN 3251, 3253), the temperature sensors before and after the DOC and DPF, and the DPF load and regeneration request. Each code names the sensor or the load condition.

FaultCheckSPN 3251FMI 0Deutz · DPF differential pressure
Plug the service tool in hereDiagnosticport, 9-pin

Where to read it

Read the active and stored faults with Deutz SerDia (or the machine maker's diagnostic tool) on the engine diagnostic plug.

What do these codes mean?

Deutz codes SPN 3248 FMI 4 to SPN 524284 FMI 12 are all about the dPF differential pressure, DPF and DOC temperature, and DPF load. The most common failure type is real condition (7 of 24); none needs an immediate stop. Start with this check: read the differential pressure in SerDia with the engine off, where it should be near zero.

How urgent are they?

None of the 24 codes here means stop now; 21 can wait until the shift ends, but find the cause before the next one; 3 are information only.

  • Check soon21
  • Info3

What should I check first?

Read the differential pressure in SerDia with the engine off, where it should be near zero

Shared checks

24 of 24

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Temperature after DPF1 code

    • Deutz SPN 3248 FMI 4Temperature after DPF: Voltage low / shorted low

      The EMR4 reads the temperature after the DPF (in the exhaust outlet of the diesel particulate filter) at a voltage below its valid window.· Shorted low
      Check soon

      Causes

      • Sensor lead chafed against the DPF housing
      • Water bridging the pins inside the temperature after the DPF connector
      • Sensor element shorted internally, so it reads as extremely hot
      • Signal wire rubbed through to the engine block or frame

      Checks

      1. 1Compare DPF outlet temperature with DOC outlet temperature on a cold engine; they should match
      2. 2Check the harness clips along the DPF for loose cable resting on hot metal
      3. 3Measure the temperature after the DPF resistance and compare it with its temperature; a very low value means the element is shorted
      4. 4Unplug the temperature after the DPF with the key on: if the code flips to the voltage-above-normal one, the harness is fine and the sensor is the shorted part
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Exhaust aftertreatment - Temperature after DPF - Voltage below normal or shorted to low source

  • DPF differential pressure5 codes

    • Deutz SPN 3251 FMI 0DPF differential pressure: Reading too high· most severe

      The DPF differential pressure (across the diesel particulate filter) reports a value above the allowed range.· Real condition
      Check soon

      Causes

      • A heavily loaded or ash-plugged DPF causes a genuine high differential pressure; check the regeneration history
      • Hose or port feeding the sensor blocked with dirt
      • Cracked or missing filter substrate leaking exhaust past the element

      Checks

      1. 1Check the real value against a mechanical gauge or second reading before touching the DPF differential pressure
      2. 2Compare with its neighbouring sensors in SerDia to see whether only this value is off
      3. 3Check the regeneration history and soot load in SerDia before touching hardware
      4. 4Inspect the sensor port or hose for restriction
      5. 5Inspect the DPF inlet and outlet pipes and the two pressure hoses for leaks, kinks and soot plugs
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - DPF differential pressure - Data above normal operational range (Most severe level)

      Full page for SPN 3251 FMI 0
    • Deutz SPN 3251 FMI 1DPF differential pressure: Reading too low· most severe

      The DPF differential pressure (across the diesel particulate filter) reports a value below the allowed range.· Real condition
      Check soon

      Causes

      • A cracked or removed DPF substrate, or a leaking or disconnected sensor hose, gives a very low reading
      • DPF differential pressure drifting low or reading with an offset
      • Hose or port feeding the sensor split or disconnected

      Checks

      1. 1Check the real value with a mechanical gauge before replacing the DPF differential pressure
      2. 2Compare with its neighbouring sensors in SerDia to see whether only this value is off
      3. 3Inspect the sensor port, hose and seal for leaks
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - DPF differential pressure - Data below normal operational range (Most severe level)

    • Deutz SPN 3253 FMI 2DPF differential pressure: Erratic reading

      The EMR4 sees the DPF differential pressure sensor (on the machine side near the diesel particulate filter, with one hose before and one after the filter) signal jump or disagree with other values.· Erratic or implausible
      Check soon

      Causes

      • Harness chafed against a bracket in a spot that only touches under vibration
      • DPF differential pressure sensor on its way out
      • Hoses swapped between inlet and outlet side

      Checks

      1. 1Watch the DPF differential pressure sensor value in SerDia while wiggling the connector and harness
      2. 2Inspect the connector for loose pins, bent terminals and moisture
      3. 3Disconnect both hoses and blow through them; condensate and soot plugs are a very common reason for DPF sensor codes
      4. 4Compare SerDia DPF differential pressure at idle with the engine warm; a value far outside what the load suggests points to hose or sensor trouble
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Exhaust aftertreatment - DPF differential pressure - Data erratic intermittent or incorrect

      Full page for SPN 3253 FMI 2
    • Deutz SPN 3253 FMI 3DPF differential pressure: Voltage high / shorted high

      The EMR4 reads the DPF differential pressure sensor (on the machine side near the diesel particulate filter, with one hose before and one after the filter) signal above its valid 0.5 to 4.5 V window.· Shorted high
      Check soon

      Causes

      • DPF differential pressure sensor failed high
      • Signal wire touching 5 V or battery in the harness
      • Pressure hoses to the DPF blocked with soot, condensate or kinked
      • Open ground return wire, which pushes the signal up to the reference

      Checks

      1. 1With the sensor unplugged, measure the signal pin; battery voltage there means a short to supply
      2. 2Compare the DPF differential pressure sensor reading in SerDia with key on and engine off against the value you expect at rest
      3. 3Check continuity of the sensor ground wire back to the EMR4 pin
      4. 4Fit a known good DPF differential pressure sensor temporarily, if you have one, and see whether the reading moves back into range
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

      Good: Open circuit (OL) between them. Any low reading is the short.

      Source wording:Exhaust aftertreatment - DPF differential pressure - Voltage above normal or shorted to high source

    • Deutz SPN 3253 FMI 4DPF differential pressure: Voltage low / shorted low

      The EMR4 reads the DPF differential pressure sensor (on the machine side near the diesel particulate filter, with one hose before and one after the filter) signal below its valid 0.5 to 4.5 V window.· Shorted low
      Check soon

      Causes

      • Signal wire rubbed through to ground
      • 5 V reference lost: open supply wire or a short on the shared 5 V line
      • Pressure hoses to the DPF blocked with soot, condensate or kinked

      Checks

      1. 1Fit a known good DPF differential pressure sensor temporarily, if you have one, and see whether the reading moves back into range
      2. 2With the sensor unplugged, measure resistance from the signal pin to ground; it should not be near zero
      3. 3Compare the DPF differential pressure sensor reading in SerDia with key on and engine off against the value you expect at rest
      4. 4Unplug other sensors sharing the 5 V line one at a time to see whether the reference comes back
      5. 5Key on: measure the 5 V reference at the DPF differential pressure sensor plug; no reference means open supply wire or another sensor on that line pulling it down
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Exhaust aftertreatment - DPF differential pressure - Voltage below normal or shorted to low source

  • Passive regeneration2 codes

    • Deutz SPN 3699 FMI 0Passive regeneration: Reading too high· most severe

      The EMR4 rates the passive regeneration (calculated by the EMR4 from the differential pressure and a soot model) as above its allowed operating range, at the most severe level.· Real condition
      Check soon

      Causes

      • The monitored condition is really above its limit, for example from overload or a blockage
      • Signal or part drifting high with age

      Checks

      1. 1Read the passive regeneration value in SerDia and compare it with an independent measurement before replacing parts
      2. 2Look for the real cause of an excessive value, such as a restriction or an overloaded function
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - Passive regeneration - Data above normal operational range (Most severe level)

    • Deutz SPN 3699 FMI 2Passive regeneration: Erratic reading

      The EMR4 sees the passive regeneration (calculated by the EMR4 from the differential pressure and a soot model) erratic, intermittent or implausible.· Erratic or implausible
      Check soon

      Causes

      • Intermittent contact in a connector or a pin with fretting
      • Harness chafed where it moves with vibration

      Checks

      1. 1Watch the passive regeneration value in SerDia while wiggling the harness and connector and note when it jumps
      2. 2Compare it with a related value, since a lone odd reading points at the circuit or part itself
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Exhaust aftertreatment - Passive regeneration - Data erratic intermittent or incorrect

  • Temperature upstream DOC1 code

    • Deutz SPN 4765 FMI 0Temperature upstream DOC: Reading too high· most severe

      The DOC inlet temperature (upstream of the diesel oxidation catalyst) (in the exhaust before the DOC) reports a temperature above the allowed operating range.· Real condition
      Check soon

      Causes

      • Partial short or wet connector lowering the DOC inlet temperature (upstream of the diesel oxidation catalyst) resistance so it reads hot
      • Sensor drifting low in resistance with age
      • Sensor harness heat-damaged where it runs along the exhaust
      • A genuine high temperature means over-fuelling, a regeneration in progress or an exhaust restriction

      Checks

      1. 1Check the real temperature with an infrared thermometer or mechanical gauge before touching the DOC inlet temperature (upstream of the diesel oxidation catalyst)
      2. 2Check the connector pins for moisture and corrosion, which can pull a reading hot
      3. 3Compare SerDia DOC inlet temperature with the sensor after the DOC; inlet should be hotter at load
      4. 4Check the connector seal and harness routing near the exhaust for heat damage
      5. 5Look in SerDia at the DOC inlet temperature (upstream of the diesel oxidation catalyst) reading next to a neighbouring temperature; a lone hot value points at the sensor
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - Temperature upstream DOC - Data above normal operational range (Most severe level)

  • Temperature downstream DOC1 code

    • Deutz SPN 4766 FMI 0Temperature downstream DOC: Reading too high· most severe

      The DOC outlet temperature (downstream of the diesel oxidation catalyst) (in the exhaust after the DOC) reports a temperature above the allowed operating range.· Real condition
      Check soon

      Causes

      • Sensor drifting low in resistance with age
      • Heat damage to the sensor lead or plug
      • A real high reading follows from a regeneration that ran too long or unburnt fuel reaching the DOC

      Checks

      1. 1Look in SerDia at the DOC outlet temperature (downstream of the diesel oxidation catalyst) reading next to a neighbouring temperature; a lone hot value points at the sensor
      2. 2Check the real temperature with an infrared thermometer or mechanical gauge before touching the DOC outlet temperature (downstream of the diesel oxidation catalyst)
      3. 3Check the sensor seal and thread for exhaust leaks that cool the reading
      4. 4Check the connector pins for moisture and corrosion, which can pull a reading hot
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - Temperature downstream DOC - Data above normal operational range (Most severe level)

  • Temperature sensor before DOC3 codes

    • Deutz SPN 4768 FMI 2Temperature sensor before DOC: Erratic reading

      The EMR4 sees the temperature sensor before the DOC (in the exhaust inlet of the DOC) jump around or disagree with other temperatures.· Erratic or implausible
      Check soon

      Causes

      • Intermittent contact in the connector or a pin with fretting
      • Moisture in the connector from condensation
      • Sensor element on its way out in the temperature sensor before the DOC
      • Harness chafed in a spot that makes contact only under vibration

      Checks

      1. 1Watch the temperature sensor before the DOC value in SerDia while wiggling the harness and connector, and note when it jumps
      2. 2Check the harness along its route for chafe, especially where it crosses a bracket
      3. 3Look at the connector and lead where they pass the exhaust flange for heat damage
      4. 4Inspect the connector for loose pins, bent terminals and moisture
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Exhaust aftertreatment - Temperature sensor before DOC - Data erratic intermittent or incorrect

    • Deutz SPN 4768 FMI 3Temperature sensor before DOC: Voltage high / shorted high

      The EMR4 reads the temperature sensor before the DOC (in the exhaust inlet of the DOC) at a voltage above its valid window.· Shorted high
      Check soon

      Causes

      • Signal wire touching a supply voltage somewhere in the harness
      • Sensor element failed open, so its resistance stays very high at any temperature
      • Open circuit: broken wire, pushed-out pin or an unplugged connector at the temperature sensor before the DOC
      • Plug and lead heat-damaged near the exhaust flange

      Checks

      1. 1Bridge the two harness pins with a jumper wire with the key on; the code should change to the voltage-below-normal one if the harness is sound
      2. 2Compare the before-DOC reading with turbine outlet or coolant temperature on a cold engine
      3. 3Unplug the temperature sensor before the DOC and measure its resistance across the two pins; an NTC that reads open at room temperature is finished
      4. 4With the sensor unplugged and key on, check the signal pin for battery voltage, which would mean a short to supply
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

      Good: Open circuit (OL) between them. Any low reading is the short.

      Source wording:Exhaust aftertreatment - Temperature sensor before DOC - Voltage above normal or shorted to high source

    • Deutz SPN 4768 FMI 4Temperature sensor before DOC: Voltage low / shorted low

      The EMR4 reads the temperature sensor before the DOC (in the exhaust inlet of the DOC) at a voltage below its valid window.· Shorted low
      Check soon

      Causes

      • Water bridging the pins inside the temperature sensor before the DOC connector
      • Sensor element shorted internally, so it reads as extremely hot
      • Plug and lead heat-damaged near the exhaust flange

      Checks

      1. 1Measure the temperature sensor before the DOC resistance and compare it with its temperature; a very low value means the element is shorted
      2. 2Look at the connector and lead where they pass the exhaust flange for heat damage
      3. 3With the EMR4 unplugged, measure resistance from the signal pin to ground; anything but open points to a short in the wire
      4. 4Unplug the temperature sensor before the DOC with the key on: if the code flips to the voltage-above-normal one, the harness is fine and the sensor is the shorted part
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Exhaust aftertreatment - Temperature sensor before DOC - Voltage below normal or shorted to low source

  • Temperature sensor after DOC3 codes

    • Deutz SPN 4769 FMI 2Temperature sensor after DOC: Erratic reading

      The EMR4 sees the temperature sensor after the DOC (in the exhaust outlet of the DOC) jump around or disagree with other temperatures.· Erratic or implausible
      Check soon

      Causes

      • Intermittent contact in the connector or a pin with fretting
      • Harness chafed in a spot that makes contact only under vibration
      • Sensor element on its way out in the temperature sensor after the DOC

      Checks

      1. 1Watch the temperature sensor after the DOC value in SerDia while wiggling the harness and connector, and note when it jumps
      2. 2Inspect the connector for loose pins, bent terminals and moisture
      3. 3Check the harness along its route for chafe, especially where it crosses a bracket
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Watch the live value on the service tool while you flex the harness and tap the connector.

      Good: A steady value that tracks the real condition. A jump while flexing is the loose pin or wire.

      Source wording:Exhaust aftertreatment - Temperature sensor after DOC - Data erratic intermittent or incorrect

    • Deutz SPN 4769 FMI 3Temperature sensor after DOC: Voltage high / shorted high

      The EMR4 reads the temperature sensor after the DOC (in the exhaust outlet of the DOC) at a voltage above its valid window.· Shorted high
      Check soon

      Causes

      • Open circuit: broken wire, pushed-out pin or an unplugged connector at the temperature sensor after the DOC
      • Sensor element failed open, so its resistance stays very high at any temperature
      • Signal wire touching a supply voltage somewhere in the harness

      Checks

      1. 1Unplug the temperature sensor after the DOC and measure its resistance across the two pins; an NTC that reads open at room temperature is finished
      2. 2Bridge the two harness pins with a jumper wire with the key on; the code should change to the voltage-below-normal one if the harness is sound
      3. 3With the sensor unplugged and key on, check the signal pin for battery voltage, which would mean a short to supply
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

      Good: Open circuit (OL) between them. Any low reading is the short.

      Source wording:Exhaust aftertreatment - Temperature sensor after DOC - Voltage above normal or shorted to high source

    • Deutz SPN 4769 FMI 4Temperature sensor after DOC: Voltage low / shorted low

      The EMR4 reads the temperature sensor after the DOC (in the exhaust outlet of the DOC) at a voltage below its valid window.· Shorted low
      Check soon

      Causes

      • Signal wire rubbed through to the engine block or frame
      • Sensor element shorted internally, so it reads as extremely hot
      • Water bridging the pins inside the temperature sensor after the DOC connector

      Checks

      1. 1Unplug the temperature sensor after the DOC with the key on: if the code flips to the voltage-above-normal one, the harness is fine and the sensor is the shorted part
      2. 2With the EMR4 unplugged, measure resistance from the signal pin to ground; anything but open points to a short in the wire
      3. 3Measure the temperature sensor after the DOC resistance and compare it with its temperature; a very low value means the element is shorted
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

      Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

      Source wording:Exhaust aftertreatment - Temperature sensor after DOC - Voltage below normal or shorted to low source

  • DPF regeneration request1 code

    • Deutz SPN 524018 FMI 14DPF regeneration request: Special instructions

      The EMR4 flags the DPF regeneration request (calculated by the EMR4 from the differential pressure and a soot model) as a special instruction case.· Other
      Info

      Causes

      • A running condition that the EMR4 monitors has been reached
      • An earlier fault left a stored special instruction

      Checks

      1. 1Read the full SerDia list and the freeze frame data
      2. 2Check the machine service manual for the instruction that belongs to this condition
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Soot load1 code

    • Deutz SPN 524022 FMI 14Soot load: Special instructions

      The EMR4 flags the soot load (calculated by the EMR4 from the differential pressure and a soot model) as a special instruction case.· Other
      Info

      Causes

      • A running condition that the EMR4 monitors has been reached
      • An earlier fault left a stored special instruction

      Checks

      1. 1Read the full SerDia list and the freeze frame data
      2. 2Check the machine service manual for the instruction that belongs to this condition
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • DOC temperature difference1 code

    • Deutz SPN 524024 FMI 11DOC temperature difference: Root cause not known

      The EMR4 logged a fault on the DOC temperature difference (in the exhaust inlet of the DOC) but could not pin down the cause.· Other
      Check soon

      Causes

      • Intermittent wiring fault that has not stayed long enough to be classified
      • Failing DOC temperature difference element
      • Poor ground or supply at the sensor

      Checks

      1. 1Read the full SerDia fault list; this code often appears next to a clearer one on the DOC temperature difference
      2. 2Measure the DOC temperature difference resistance and compare with a temperature table
      3. 3Inspect the DOC temperature difference connector and the harness run for chafed insulation, bent pins and moisture
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • DPF ash load1 code

    • Deutz SPN 524134 FMI 0DPF ash load: Reading too high· most severe

      The EMR4 rates the DPF ash load (calculated by the EMR4 from the differential pressure and a soot model) as above its allowed operating range, at the most severe level.· Real condition
      Check soon

      Causes

      • The monitored condition is really above its limit, for example from overload or a blockage
      • Signal or part drifting high with age

      Checks

      1. 1Read the DPF ash load value in SerDia and compare it with an independent measurement before replacing parts
      2. 2Look for the real cause of an excessive value, such as a restriction or an overloaded function
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - DPF ash load - Data above normal operational range (Most severe level)

  • DPF soot load2 codes

    • Deutz SPN 524135 FMI 0DPF soot load: Reading too high· most severe

      The EMR4 rates the DPF soot load (calculated by the EMR4 from the differential pressure and a soot model) as above its allowed operating range, at the most severe level.· Real condition
      Check soon

      Causes

      • The monitored condition is really above its limit, for example from overload or a blockage
      • Signal or part drifting high with age

      Checks

      1. 1Read the DPF soot load value in SerDia and compare it with an independent measurement before replacing parts
      2. 2Look for the real cause of an excessive value, such as a restriction or an overloaded function
      allowed rangetime
      The reading against the band the controller allows.

      Meter test

      Check the real value with a separate gauge or thermometer before blaming the sensor.

      Good: If the gauge agrees with the display, fix the machine, not the sensor.

      Source wording:Exhaust aftertreatment - DPF soot load - Data above normal operational range (Most severe level)

    • Deutz SPN 524135 FMI 14DPF soot load: Special instructions

      The EMR4 flags the DPF soot load (calculated by the EMR4 from the differential pressure and a soot model) as a special instruction case.· Other
      Info

      Causes

      • A running condition that the EMR4 monitors has been reached
      • An earlier fault left a stored special instruction

      Checks

      1. 1Read the full SerDia list and the freeze frame data
      2. 2Check the machine service manual for the instruction that belongs to this condition
      ControllerPartSupplySignalGround
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Read the code with the service tool and note which other codes are active with it.

      Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Swapped hoses for differential pressure sensor DPF1 code

    • Deutz SPN 524283 FMI 12Swapped hoses for differential pressure sensor DPF: Bad device or component

      The EMR4 judges the swapped hoses for differential pressure sensor DPF (on the machine side near the diesel particulate filter, with one hose before and one after the filter) to be a bad device.· Part or controller
      Check soon

      Causes

      • Internal failure of the swapped hoses for differential pressure sensor DPF
      • Water or oil inside the sensor

      Checks

      1. 1Check the 5 V supply and signal at the swapped hoses for differential pressure sensor DPF plug
      2. 2Replace with a known good sensor and see whether the code clears
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Exhaust aftertreatment - Swapped hoses for differential pressure sensor DPF - Bad intelligent device or component

  • DOC removed1 code

    • Deutz SPN 524284 FMI 12DOC removed: Bad device or component

      The EMR4 judges the DOC removed (in the exhaust inlet of the DOC) to be a bad device.· Part or controller
      Check soon

      Causes

      • Internal failure of the part or its electronics
      • Water, soot or dirt inside the part

      Checks

      1. 1Read the DOC removed status in SerDia and run any available actuator or component test
      2. 2Check supply voltage and ground at the connector with the key on to confirm it is powered
      ControllerPartSupplySignalGround?
      Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

      Meter test

      Check power and ground at the module connector with the key on, then its fuses.

      Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

      Source wording:Exhaust aftertreatment - DOC removed - Bad intelligent device or component

Shared checks

Checks, in order

  1. 1Read the differential pressure in SerDia with the engine off, where it should be near zero
  2. 2Check the two sensing hoses for blockage and correct routing
  3. 3Compare the temperature sensors before and after the DOC and DPF for a plausible difference
  4. 4Inspect the sensor connectors for heat damage
  5. 5Check whether a regeneration was requested and what blocked it

Causes

  • Differential pressure hose blocked, split or swapped
  • Temperature sensor in the hot exhaust with burnt wiring or a corroded plug
  • Filter really loaded because regeneration did not run
  • Fault in the sensor, its 5 V supply or its ground wire

Most common here: real condition (7 of 24)

Check the real value with a separate gauge or thermometer before blaming the sensor.

When to stop

You'll notice: A warning lamp or limited function.

Repeated aftertreatment faults lead to an engine derate. Parked regenerations and dosing tests are run with the service tool; do not remove or bypass DPF or SCR parts.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.

Machine down?

Get a replacement machine or a technician - suppliers in the UAE contact you.

Post a request
EquipmentsFinder

Need equipment? Have equipment?

Buyers post one request and get quotes from suppliers. Suppliers list free and reach active demand.