Deutz · Exhaust aftertreatment (SCR)
Deutz DEF line, tank and SCR heaters fault codes
The heaters that thaw frozen DEF: the heated DEF lines, the tank heating valve and heater, and the SCR module heating circuit. Each code names the heater circuit and whether it is shorted high, shorted low, open or faulty.
Where to read it
Read the active and stored faults with Deutz SerDia (or the machine maker's diagnostic tool) on the engine diagnostic plug.
What do these codes mean?
Deutz codes SPN 4243 FMI 11 to SPN 524063 FMI 12 are all about the dEF line, tank and SCR heaters. The most common failure type is shorted high (6 of 23); none needs an immediate stop. Start with this check: measure the heater or valve coil resistance for the part named in the code.
How urgent are they?
None of the 23 codes here means stop now; all 23 can wait until the shift ends, but find the cause before the next one.
- Check soon23
What should I check first?
Measure the heater or valve coil resistance for the part named in the code
Shared checks23 of 23
Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet
SCR heater4 codes
Deutz SPN 4243 FMI 11SCR heater: Root cause not known
The EMR4 logged a fault on the SCR heater (in the SCR dosing module heating circuit) but could not classify the cause. Test the circuit and the part separately. Deutz list: KWP code 1089, blink code 7-8-3. For this code the controller flagged the SCR heater but could not tell whether wiring, part or supply is to blame. The SCR heater warms the SCR dosing module so it can work in the cold. The usual symptom is a lamp with little else to notice, because the controller could not name the cause.· Lost messageLost messageCheck soonCauses
- Intermittent wiring fault
- Failing SCR heater
- Intermittent contact that left no clear electrical signature
Checks
- 1Read the full SerDia fault list; this code often sits next to a clearer one on the SCR heater
- 2Measure the supply and ground at the SCR heater plug with the key on to confirm it is powered
- 3Inspect the SCR heater plug and harness for chafed insulation, bent pins and moisture
- 4Read the freeze frame stored with the SCR heater fault and note speed, load and battery voltage at the moment it was logged.
- 5Measure the resistance of the SCR heater at its connector.
- 6Check the SCR heater fuse and its relay before testing the heater element.
Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end. Meter test
Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.
Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.
Deutz SPN 523719 FMI 3SCR heater: Voltage high / shorted high
The EMR4 sees the output for the SCR heater (in the SCR dosing module heating circuit) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the actuator correctly. Deutz list: KWP code 1108, blink code 672. For this code the controller read the SCR heater circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. The SCR heater warms the SCR dosing module so it can work in the cold. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- Output wire shorted to battery positive
- Connector pin touching a live pin
- SCR heater shorted internally
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Unplug the SCR heater: if the code stays, the short is in the harness or the EMR4; if it clears, the part is the shorted one
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Measure the winding or coil resistance of the part
- 4With the EMR4 and the SCR heater unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Measure the resistance of the SCR heater at its connector.
- 6Check the SCR heater fuse and its relay before testing the heater element.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - SCR heater - Voltage above normal or shorted to high source
Deutz SPN 523719 FMI 4SCR heater: Voltage low / shorted low
The EMR4 sees the output for the SCR heater (in the SCR dosing module heating circuit) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the actuator correctly. Deutz list: KWP code 1109, blink code 672. For this code the controller read the SCR heater circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. The SCR heater warms the SCR dosing module so it can work in the cold. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Output wire chafed to ground or the engine block
- SCR heater winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Unplug the SCR heater: if the code changes, the part is the shorted one; if it stays, look at the harness
- 2With the EMR4 unplugged, measure the output wire to ground; it should not be low ohms
- 3Measure the winding resistance of the part and look for a very low value
- 4With the connector unplugged, measure the SCR heater signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 5Measure the resistance of the SCR heater at its connector.
- 6Check the SCR heater fuse and its relay before testing the heater element.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - SCR heater - Voltage below normal or shorted to low source
Deutz SPN 523719 FMI 5SCR heater: Current low / open circuit
The EMR4 sees too little current through the SCR heater (in the SCR dosing module heating circuit), which means the circuit is open. The controller commands the actuator but nothing flows. Deutz list: KWP codes 1087 (blink 6-7-2), 1106 (blink 672). For this code the controller measured too little current in the SCR heater circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. The SCR heater warms the SCR dosing module so it can work in the cold. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Broken wire or a pin pushed out of the connector
- SCR heater winding open
- Connector left unplugged after earlier work
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Measure the resistance across the SCR heater terminals: infinity means an open winding
- 2Continuity-test each wire to the matching EMR4 pin
- 3Inspect both ends of the SCR heater circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 4Check the continuity of both wires between the EMR4 plug and the SCR heater connector, then the coil resistance, to separate a broken wire from a dead coil.
- 5Measure the resistance of the SCR heater at its connector.
- 6Check the SCR heater fuse and its relay before testing the heater element.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - SCR heater - Current below normal or open circuit
DEF suction line heater relay3 codes
Deutz SPN 4341 FMI 3DEF suction line heater relay: Voltage high / shorted high
The EMR4 sees the output for the DEF suction line heater relay (in the DEF suction line heater circuit) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the relay or output correctly. Deutz list: KWP code 1104, blink code 675. For this code the controller read the DEF suction line heater relay circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. The suction line heater relay powers the heater on the pickup line in the DEF tank. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- Output wire shorted to battery positive
- Connector pin touching a live pin
- DEF suction line heater relay shorted internally
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Unplug the DEF suction line heater relay: if the code stays, the short is in the harness or the EMR4; if it clears, the part is the shorted one
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Measure the winding or coil resistance of the part
- 4With the EMR4 and the DEF suction line heater relay unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Check the relay of the suction line heater and its fuse.
- 6Measure the voltage at the suction line heater relay output while heating is commanded in cold conditions.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - DEF suction line heater relay - Voltage above normal or shorted to high source
Deutz SPN 4341 FMI 4DEF suction line heater relay: Voltage low / shorted low
The EMR4 sees the output for the DEF suction line heater relay (in the DEF suction line heater circuit) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the relay or output correctly. Deutz list: KWP code 1105, blink code 675. For this code the controller read the DEF suction line heater relay circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. The suction line heater relay powers the heater on the pickup line in the DEF tank. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Output wire chafed to ground or the engine block
- DEF suction line heater relay winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Unplug the DEF suction line heater relay: if the code changes, the part is the shorted one; if it stays, look at the harness
- 2With the EMR4 unplugged, measure the output wire to ground; it should not be low ohms
- 3Measure the winding resistance of the part and look for a very low value
- 4With the connector unplugged, measure the DEF suction line heater relay signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 5Check the relay of the suction line heater and its fuse.
- 6Measure the voltage at the suction line heater relay output while heating is commanded in cold conditions.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - DEF suction line heater relay - Voltage below normal or shorted to low source
Deutz SPN 4341 FMI 5DEF suction line heater relay: Current low / open circuit
The EMR4 sees too little current through the DEF suction line heater relay (in the DEF suction line heater circuit), which means the circuit is open. The controller commands the relay or output but nothing flows. Deutz list: KWP codes 1086 (blink 6-7-5), 1102 (blink 675). For this code the controller measured too little current in the DEF suction line heater relay circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. The suction line heater relay powers the heater on the pickup line in the DEF tank. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Broken wire or a pin pushed out of the connector
- DEF suction line heater relay winding open
- Connector left unplugged after earlier work
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Measure the resistance across the DEF suction line heater relay terminals: infinity means an open winding
- 2Continuity-test each wire to the matching EMR4 pin
- 3Inspect both ends of the DEF suction line heater relay circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 4Check the continuity of both wires between the EMR4 plug and the DEF suction line heater relay connector, then the coil resistance, to separate a broken wire from a dead coil.
- 5Check the relay of the suction line heater and its fuse.
- 6Measure the voltage at the suction line heater relay output while heating is commanded in cold conditions.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - DEF suction line heater relay - Current below normal or open circuit
Heater DEF pressure line4 codes
Deutz SPN 4343 FMI 3Heater DEF pressure line: Voltage high / shorted high
The EMR4 sees the output for the DEF pressure line heater (on the DEF pressure line between pump and dosing valve) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the actuator correctly. Deutz list: KWP code 1096, blink code 673. For this code the controller read the heater DEF pressure line circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. This is the heater on the DEF pressure line from the pump to the dosing module. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- Output wire shorted to battery positive
- Connector pin touching a live pin
- DEF pressure line heater shorted internally
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Unplug the DEF pressure line heater: if the code stays, the short is in the harness or the EMR4; if it clears, the part is the shorted one
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Measure the winding or coil resistance of the part
- 4With the EMR4 and the heater DEF pressure line unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Trace the heater wire along the pressure line for damage.
- 6Measure the current of the pressure line heater when it is switched on and compare it with the return line heater.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - Heater DEF pressure line - Voltage above normal or shorted to high source
Deutz SPN 4343 FMI 4Heater DEF pressure line: Voltage low / shorted low
The EMR4 sees the output for the DEF pressure line heater (on the DEF pressure line between pump and dosing valve) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the actuator correctly. Deutz list: KWP code 1097, blink code 673. For this code the controller read the heater DEF pressure line circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. This is the heater on the DEF pressure line from the pump to the dosing module. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Output wire chafed to ground or the engine block
- DEF pressure line heater winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Unplug the DEF pressure line heater: if the code changes, the part is the shorted one; if it stays, look at the harness
- 2With the EMR4 unplugged, measure the output wire to ground; it should not be low ohms
- 3Measure the winding resistance of the part and look for a very low value
- 4With the connector unplugged, measure the heater DEF pressure line signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 5Trace the heater wire along the pressure line for damage.
- 6Measure the current of the pressure line heater when it is switched on and compare it with the return line heater.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - Heater DEF pressure line - Voltage below normal or shorted to low source
Deutz SPN 4343 FMI 5Heater DEF pressure line: Current low / open circuit
The EMR4 sees too little current through the DEF pressure line heater (on the DEF pressure line between pump and dosing valve), which means the circuit is open. The controller commands the actuator but nothing flows. Deutz list: KWP codes 1083 (blink 6-7-3), 1094 (blink 673). For this code the controller measured too little current in the heater DEF pressure line circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. This is the heater on the DEF pressure line from the pump to the dosing module. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Broken wire or a pin pushed out of the connector
- DEF pressure line heater winding open
- Connector left unplugged after earlier work
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Measure the resistance across the DEF pressure line heater terminals: infinity means an open winding
- 2Continuity-test each wire to the matching EMR4 pin
- 3Inspect both ends of the DEF pressure line heater circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 4Check the continuity of both wires between the EMR4 plug and the heater DEF pressure line connector, then the coil resistance, to separate a broken wire from a dead coil.
- 5Trace the heater wire along the pressure line for damage.
- 6Measure the current of the pressure line heater when it is switched on and compare it with the return line heater.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - Heater DEF pressure line - Current below normal or open circuit
Deutz SPN 4343 FMI 11Heater DEF pressure line: Root cause not known
The EMR4 logged a fault on the DEF pressure line heater (on the DEF pressure line between pump and dosing valve) but could not classify the cause. Test the circuit and the part separately. Deutz list: KWP code 893, blink code 8-7-1. For this code the controller flagged the heater DEF pressure line but could not tell whether wiring, part or supply is to blame. This is the heater on the DEF pressure line from the pump to the dosing module. The usual symptom is a lamp with little else to notice, because the controller could not name the cause.· OtherOtherCheck soonCauses
- Intermittent wiring fault
- Failing DEF pressure line heater
- Intermittent contact that left no clear electrical signature
Checks
- 1Read the full SerDia fault list; this code often sits next to a clearer one on the DEF pressure line heater
- 2Measure the supply and ground at the DEF pressure line heater plug with the key on to confirm it is powered
- 3Inspect the DEF pressure line heater plug and harness for chafed insulation, bent pins and moisture
- 4Read the freeze frame stored with the heater DEF pressure line fault and note speed, load and battery voltage at the moment it was logged.
- 5Trace the heater wire along the pressure line for damage.
- 6Measure the current of the pressure line heater when it is switched on and compare it with the return line heater.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Heater DEF return line4 codes
Deutz SPN 4345 FMI 3Heater DEF return line: Voltage high / shorted high
The EMR4 sees the output for the DEF return line heater (on the DEF return line from the dosing module to the tank) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the actuator correctly. Deutz list: KWP code 1092, blink code 674. For this code the controller read the heater DEF return line circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. This is the heater on the DEF return line, which keeps the return flow from freezing. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- Output wire shorted to battery positive
- Connector pin touching a live pin
- DEF return line heater shorted internally
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Unplug the DEF return line heater: if the code stays, the short is in the harness or the EMR4; if it clears, the part is the shorted one
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Measure the winding or coil resistance of the part
- 4With the EMR4 and the heater DEF return line unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Trace the heater wire along the return line for damage.
- 6Measure the current of the return line heater when it is switched on; a heater drawing no current is open.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - Heater DEF return line - Voltage above normal or shorted to high source
Deutz SPN 4345 FMI 4Heater DEF return line: Voltage low / shorted low
The EMR4 sees the output for the DEF return line heater (on the DEF return line from the dosing module to the tank) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the actuator correctly. Deutz list: KWP code 1093, blink code 674. For this code the controller read the heater DEF return line circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. This is the heater on the DEF return line, which keeps the return flow from freezing. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Output wire chafed to ground or the engine block
- DEF return line heater winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Unplug the DEF return line heater: if the code changes, the part is the shorted one; if it stays, look at the harness
- 2With the EMR4 unplugged, measure the output wire to ground; it should not be low ohms
- 3Measure the winding resistance of the part and look for a very low value
- 4With the connector unplugged, measure the heater DEF return line signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 5Trace the heater wire along the return line for damage.
- 6Measure the current of the return line heater when it is switched on; a heater drawing no current is open.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - Heater DEF return line - Voltage below normal or shorted to low source
Deutz SPN 4345 FMI 5Heater DEF return line: Current low / open circuit
The EMR4 sees too little current through the DEF return line heater (on the DEF return line from the dosing module to the tank), which means the circuit is open. The controller commands the actuator but nothing flows. Deutz list: KWP codes 1081 (blink 6-7-4), 1090 (blink 674). For this code the controller measured too little current in the heater DEF return line circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. This is the heater on the DEF return line, which keeps the return flow from freezing. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Broken wire or a pin pushed out of the connector
- DEF return line heater winding open
- Connector left unplugged after earlier work
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Measure the resistance across the DEF return line heater terminals: infinity means an open winding
- 2Continuity-test each wire to the matching EMR4 pin
- 3Inspect both ends of the DEF return line heater circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 4Check the continuity of both wires between the EMR4 plug and the heater DEF return line connector, then the coil resistance, to separate a broken wire from a dead coil.
- 5Trace the heater wire along the return line for damage.
- 6Measure the current of the return line heater when it is switched on; a heater drawing no current is open.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - Heater DEF return line - Current below normal or open circuit
Deutz SPN 4345 FMI 11Heater DEF return line: Root cause not known
The EMR4 logged a fault on the DEF return line heater (on the DEF return line from the dosing module to the tank) but could not classify the cause. Test the circuit and the part separately. Deutz list: KWP code 892, blink code 2-3-6. For this code the controller flagged the heater DEF return line but could not tell whether wiring, part or supply is to blame. This is the heater on the DEF return line, which keeps the return flow from freezing. The usual symptom is a lamp with little else to notice, because the controller could not name the cause.· OtherOtherCheck soonCauses
- Intermittent wiring fault
- Failing DEF return line heater
- Intermittent contact that left no clear electrical signature
Checks
- 1Read the full SerDia fault list; this code often sits next to a clearer one on the DEF return line heater
- 2Measure the supply and ground at the DEF return line heater plug with the key on to confirm it is powered
- 3Inspect the DEF return line heater plug and harness for chafed insulation, bent pins and moisture
- 4Read the freeze frame stored with the heater DEF return line fault and note speed, load and battery voltage at the moment it was logged.
- 5Trace the heater wire along the return line for damage.
- 6Measure the current of the return line heater when it is switched on; a heater drawing no current is open.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
DEF tank heating valve3 codes
Deutz SPN 4366 FMI 3DEF tank heating valve: Voltage high / shorted high
The EMR4 sees the output for the DEF tank heating valve (in the SCR dosing module heating circuit) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the actuator correctly. Deutz list: KWP code 1112, blink code 671. For this code the controller read the DEF tank heating valve circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. The tank heating valve lets hot coolant into the DEF tank to thaw it. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- Output wire shorted to battery positive
- Connector pin touching a live pin
- DEF tank heating valve shorted internally
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Unplug the DEF tank heating valve: if the code stays, the short is in the harness or the EMR4; if it clears, the part is the shorted one
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Measure the winding or coil resistance of the part
- 4With the EMR4 and the DEF tank heating valve unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Check that coolant reaches the heating valve and that it switches.
- 6Feel the coolant hoses at the tank heating valve: one side should warm when the valve opens.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - DEF tank heating valve - Voltage above normal or shorted to high source
Deutz SPN 4366 FMI 4DEF tank heating valve: Voltage low / shorted low
The EMR4 sees the output for the DEF tank heating valve (in the SCR dosing module heating circuit) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the actuator correctly. Deutz list: KWP code 1113, blink code 671. For this code the controller read the DEF tank heating valve circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. The tank heating valve lets hot coolant into the DEF tank to thaw it. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Output wire chafed to ground or the engine block
- DEF tank heating valve winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Unplug the DEF tank heating valve: if the code changes, the part is the shorted one; if it stays, look at the harness
- 2With the EMR4 unplugged, measure the output wire to ground; it should not be low ohms
- 3Measure the winding resistance of the part and look for a very low value
- 4With the connector unplugged, measure the DEF tank heating valve signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 5Check that coolant reaches the heating valve and that it switches.
- 6Feel the coolant hoses at the tank heating valve: one side should warm when the valve opens.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - DEF tank heating valve - Voltage below normal or shorted to low source
Deutz SPN 4366 FMI 5DEF tank heating valve: Current low / open circuit
The EMR4 sees too little current through the DEF tank heating valve (in the SCR dosing module heating circuit), which means the circuit is open. The controller commands the actuator but nothing flows. Deutz list: KWP codes 1082 (blink 7-6-2), 1084 (blink 7-6-2), 1085 (blink 7-6-2), 1088 (blink 6-7-1), 1110 (blink 671). For this code the controller measured too little current in the DEF tank heating valve circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. The tank heating valve lets hot coolant into the DEF tank to thaw it. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Broken wire or a pin pushed out of the connector
- DEF tank heating valve winding open
- Connector left unplugged after earlier work
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Measure the resistance across the DEF tank heating valve terminals: infinity means an open winding
- 2Continuity-test each wire to the matching EMR4 pin
- 3Inspect both ends of the DEF tank heating valve circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 4Check the continuity of both wires between the EMR4 plug and the DEF tank heating valve connector, then the coil resistance, to separate a broken wire from a dead coil.
- 5Check that coolant reaches the heating valve and that it switches.
- 6Feel the coolant hoses at the tank heating valve: one side should warm when the valve opens.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - DEF tank heating valve - Current below normal or open circuit
DEF tank heater1 code
Deutz SPN 523981 FMI 11DEF tank heater: Root cause not known
The EMR4 logged a fault on the DEF tank heater (in the SCR dosing module heating circuit) but could not classify the cause. Test the circuit and the part separately. Deutz list: KWP code 918, blink code 2-4-3. For this code the controller flagged the DEF tank heater but could not tell whether wiring, part or supply is to blame. The tank heater is the electric heater inside the DEF tank unit. The usual symptom is a lamp with little else to notice, because the controller could not name the cause.· OtherOtherCheck soonCauses
- Intermittent wiring fault
- Failing DEF tank heater
- Intermittent contact that left no clear electrical signature
Checks
- 1Read the full SerDia fault list; this code often sits next to a clearer one on the DEF tank heater
- 2Measure the supply and ground at the DEF tank heater plug with the key on to confirm it is powered
- 3Inspect the DEF tank heater plug and harness for chafed insulation, bent pins and moisture
- 4Read the freeze frame stored with the DEF tank heater fault and note speed, load and battery voltage at the moment it was logged.
- 5Check the tank unit connector for DEF corrosion.
- 6Compare the tank temperature rise in SerDia with the heater state after a cold soak.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
DEF heater4 codes
Deutz SPN 524063 FMI 3DEF heater: Voltage high / shorted high
The EMR4 sees the output for the DEF heater (in the DEF tank or line that keeps the DEF thawed) at a voltage above normal, as if the circuit is shorted to the battery supply. The controller cannot drive the actuator correctly. Deutz list: KWP code 1558, blink code 869. For this code the controller read the DEF heater circuit at a voltage above normal, as if the wire or the driver were pulled up to the supply voltage, for instance by a chafed harness touching a live wire. The DEF heater is a general heater output of the SCR system. The usual symptom is a load that stays energised or never switches off, and the lamp comes on at the next key cycle.· Shorted highShorted highCheck soonCauses
- DEF heater shorted internally
- Output wire shorted to battery positive
- Heater element open or shorted
- Connector pin touching a live pin
- Harness insulation worn through where it rubs on a bracket, letting the wire touch a live supply
Checks
- 1Measure the heater element resistance and check its fuse
- 2With the EMR4 unplugged, measure the output wire to battery positive; it should be open
- 3Check the heater wiring at the tank unit connector for corrosion
- 4With the EMR4 and the DEF heater unplugged, measure the signal wire against battery positive; it must read open, and any reading means the harness is shorted high.
- 5Measure the DEF heater element resistance.
- 6Check the shared heater supply fuse, which can take several DEF heaters out together.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Source wording:Exhaust aftertreatment - DEF heater - Voltage above normal or shorted to high source
Deutz SPN 524063 FMI 4DEF heater: Voltage low / shorted low
The EMR4 sees the output for the DEF heater (in the DEF tank or line that keeps the DEF thawed) at a voltage below normal, as if the circuit is shorted to ground. The controller cannot drive the actuator correctly. Deutz list: KWP code 1559, blink code 869. For this code the controller read the DEF heater circuit at a voltage below normal, as if it were tied to ground, which points to a wire rubbing through on the frame or a part shorted to its housing. The DEF heater is a general heater output of the SCR system. The usual symptom is a load that never switches on, a dead function and a lamp after a few seconds.· Shorted lowShorted lowCheck soonCauses
- Heater element open or shorted
- Output wire chafed to ground or the engine block
- DEF heater winding shorted to its housing
- Water in the connector bridging the pins
- Wire pinched against the engine block or frame so the signal is pulled to ground
Checks
- 1Measure the winding resistance of the part and look for a very low value
- 2Measure the heater element resistance and check its fuse
- 3Unplug the DEF heater: if the code changes, the part is the shorted one; if it stays, look at the harness
- 4Check the heater wiring at the tank unit connector for corrosion
- 5With the connector unplugged, measure the DEF heater signal wire against ground; a low resistance means a harness short, while an open reading sends you to the part itself.
- 6Check the shared heater supply fuse, which can take several DEF heaters out together.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Source wording:Exhaust aftertreatment - DEF heater - Voltage below normal or shorted to low source
Deutz SPN 524063 FMI 5DEF heater: Current low / open circuit
The EMR4 sees too little current through the DEF heater (in the DEF tank or line that keeps the DEF thawed), which means the circuit is open. The controller commands the actuator but nothing flows. Deutz list: KWP code 1555, blink code 869. For this code the controller measured too little current in the DEF heater circuit, the signature of an open wire, a pulled-out pin or a burnt-out coil. The DEF heater is a general heater output of the SCR system. The usual symptom is a load that does not respond at all although the controller commands it.· Open circuitOpen circuitCheck soonCauses
- Heater element open or shorted
- Connector left unplugged after earlier work
- Broken wire or a pin pushed out of the connector
- Terminal pushed back or corroded in its connector so the circuit is open
Checks
- 1Continuity-test each wire to the matching EMR4 pin
- 2Measure the resistance across the DEF heater terminals: infinity means an open winding
- 3Check the heater wiring at the tank unit connector for corrosion
- 4Inspect both ends of the DEF heater circuit (EMR4 plug and part connector) for pins pushed back in the housing
- 5Check the continuity of both wires between the EMR4 plug and the DEF heater connector, then the coil resistance, to separate a broken wire from a dead coil.
- 6Check the shared heater supply fuse, which can take several DEF heaters out together.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Source wording:Exhaust aftertreatment - DEF heater - Current below normal or open circuit
Deutz SPN 524063 FMI 12DEF heater: Bad device or component
The EMR4 judges the DEF heater (in the DEF tank or line that keeps the DEF thawed) to be a bad device, meaning the part or its driver electronics no longer respond as a working component. Deutz list: KWP codes 1646 and 1647, blink code 869. For this code the DEF heater reports an internal fault to the controller, so the electronics inside the part have judged themselves defective. The DEF heater is a general heater output of the SCR system. The usual symptom is a function that stops at once and will not come back until the part is replaced.· Part or controllerPart or controllerCheck soonCauses
- Internal failure of the DEF heater
- Water or soot inside the part
- Driver stage in the EMR4 failing
- Electronics inside the part damaged by heat, water or a voltage spike
Checks
- 1Read the DEF heater status in SerDia and run any actuator test
- 2Measure supply voltage and ground at the DEF heater connector with the key on to confirm the part is powered
- 3Fit a known good DEF heater if you can borrow one and see whether the code clears for good
- 4Check supply voltage and ground at the DEF heater connector under load; if both are good the part itself is the likely culprit and a swap with a known good one confirms it.
- 5Measure the DEF heater element resistance.
- 6Check the shared heater supply fuse, which can take several DEF heaters out together.
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Check power and ground at the module connector with the key on, then its fuses.
Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.
Source wording:Exhaust aftertreatment - DEF heater - Bad intelligent device or component
Shared checks
Checks, in order
- 1Measure the heater or valve coil resistance for the part named in the code
- 2Check the heating valve and relay for supply and ground
- 3Inspect the connectors for crystallised DEF
- 4Check that coolant reaches the tank heating valve and that the valve switches in cold conditions
Causes
- Heater element open or shorted
- Heater valve or relay failed
- Connector corroded by DEF
- Coolant flow to the tank heating valve restricted
Most common here: shorted high (6 of 23)
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
When to stop
You'll notice: A warning lamp or limited function.
Repeated aftertreatment faults lead to an engine derate. Parked regenerations and dosing tests are run with the service tool; do not remove or bypass DPF or SCR parts.
Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.
Related on Equipments Finder
Sources
Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.