JLG · Communication
JLG Fault Code 6‑6
CAN bus failure
What does JLG code 6-6 mean?
The ground module and platform module are no longer exchanging CAN messages, usually from wiring trouble between the platform and ground station. Controls stop responding. Urgency: stop now - shut down and fix before working on. Check first: measure the resistance across CAN high and low at the T fitting in the ground station; about 60 ohms means a complete bus.
Can I keep running with it?
Stop now
Shut down and fix before working on. Running on risks damage or the machine locks out.
What should I check first?
Measure the resistance across CAN high and low at the T fitting in the ground station; about 60 ohms means a complete bus
Then 4 more checksWhere this code shows
Turn the key on and watch the fault lamp or platform display.
Checks
0 of 5 done
Causes
- CAN wires chafed or broken in the boom cable track or at the turntable
- Corroded CAN connector at the platform or ground module
- Open terminating resistor or damaged T fitting at the ground station
- Low supply voltage causing a module reset
1 more causeFewer causes
- Failed platform or ground module
How it failed
You'll notice: The platform controls stop responding because the ground and platform modules are no longer talking, and the lamp flashes 6-6.
Lost messageRead from how the source describes the code
A module stopped hearing another on the data link, or the data came late or garbled.
- Meter test
- Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.
- Good result
- About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.
When to stop
Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.
Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.
Same part, other failures: Controller, CAN bus, software, configuration and reference voltage
6 other codes on this part are also lost message (662, 663, 666, 6613 and more). When they show together, start at the wiring and connector they share.
- 6-6CAN bus failureLost messageStop now
- 9-9Controller (module) problemPart or controllerStop now
- 662CAN bus failure - platform moduleLost messageStop now
- 663CAN bus failure - load sensing system moduleLost messageCheck soon
- 666CAN bus failure - engine controllerLost messageStop now
- 998EEPROM failure - check all settingsPart or controllerStop now
- 6613CAN bus failure - excessive CAN bus errorsLost messageCheck soon
- 6622CAN bus failure - TCU moduleLost messageCheck soon
- 6629CAN bus failure - telematics CAN bus loading too highLost messageCheck soon
Show the other 13 codesHide the other codes
- 9910Functions locked out - platform module software version improperPart or controllerStop now
- 9911Functions locked out - LSS module software version improperPart or controllerStop now
- 9919Ground sensor reference voltage out of rangeOtherStop now
- 9920Platform sensor ref voltage out of rangeOtherStop now
- 9921Ground module failure - high side driver cutout faultyPart or controllerStop now
- 9922Platform module failure - HWFS code 1Part or controllerStop now
- 9924Functions locked out - machine not configuredOtherStop now
- 9927Ground module constant data update requiredPart or controllerCheck soon
- 9944Current feedback gains out of rangeOtherCheck soon
- 9945Current feedback calibration checksum incorrectPart or controllerCheck soon
- 9949Machine configuration out of range - check all settingsOtherCheck soon
- 9979Functions locked out - ground module software version improperPart or controllerStop now
- 9986Ground module Vlow FET failureOtherStop now
Related on Equipments Finder
Source
JLG 600S/600SJ/660SJ/600A/AJ Service and Maintenance Manual 3120840, section 6 (Tables 6-3, 6-5)
This source lists 6-6 and its meaning. The guidance on this page is general, not taken from it.
The source covers: JLG boom lifts with the JLG Control System (600S, 600SJ, 660SJ, 600A/AJ, 450A, 510A, 400S, 1200/1350SJP families).
Checks, causes, the drawing and the meter test are general workshop guidance, not the maker's procedure. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.