Thermo King · Temperature sensors (SR-2/SR-3/SR-4)

Thermo King Evaporator, air and compressor temperature sensors fault codes

This page covers the unit temperature sensors: evaporator, return and discharge air sensors, their fall-back, range and shutdown alarms, and the compressor temperature sensors. The controller measures the temperature of the evaporator coil, the return air, the discharge air and the ambient air with thermistor probes.

More about these parts

When a probe is missing or out of range the controller can fall back to a substitute sensor or, if it has none, shut the unit or the zone down. A thermistor on the compressor head or discharge reports the temperature the compressor runs at.

FaultCheck02Thermo King · Evaporator, air and compressor temperature sensors
Code shows hereFAULT02

Where this code shows

Press the alarm key or open the Alarms menu on the controller display to list active alarms.

What do these codes mean?

Thermo King codes P1E to 204 are all about the evaporator, air and compressor temperature sensors. 4 need an immediate stop. Start with this check: find the named probe and trace its lead to the unit harness for damage and pinched spots.

How urgent are they?

4 of 21 codes here mean stop now; 15 can wait until the shift ends, but find the cause before the next one; 2 are information only.

  • Stop now4
  • Check soon15
  • Info2

What should I check first?

Find the named probe and trace its lead to the unit harness for damage and pinched spots

Shared checks

21 of 21

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Thermo King P1EReturn air temperature sensor fault

    The return air temperature sensor of an older controller is faulty.· Other
    Check soon

    Causes

    • Sensor lead damaged
    • Sensor failed

    Checks

    1. 1Check the sensor plug and lead
    2. 2Measure the sensor resistance
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 02Check evaporator coil sensor

    The controller reads the evaporator coil temperature sensor outside its valid range, so it cannot see frost building on the coil.· Other
    Check soon

    Causes

    • Coil sensor wire chafed or cut where it leaves the evaporator
    • Sensor connector at the controller corroded or pushed back
    • Sensor probe itself open or shorted internally
    • Water in the splice protected by the heat-shrink at the coil

    Checks

    1. 1Find the coil sensor on the evaporator and trace its leads to the unit harness for damage
    2. 2Unplug the sensor and read its resistance at the pins
    3. 3an open or near-zero reading means the sensor is dead
    4. 4Compare the reading to a known-good sensor at the same temperature, since sensors of one type should match
    5. 5Check the connector at the controller for green corrosion and tug each wire in the plug
    6. 6Clear the alarm and run a defrost to see if it returns immediately
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King P2ERemote return air temperature sensor fault

    The remote return air sensor is faulty.· Other
    Check soon

    Causes

    • Sensor lead damaged
    • Sensor failed

    Checks

    1. 1Check the sensor plug and lead
    2. 2Measure the sensor resistance
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 03Check return air sensor

    The return air sensor reading is out of range, which means the controller does not know the real box air temperature.· Other
    Stop now

    Causes

    • Return air sensor in the evaporator inlet damaged by cargo or forklift
    • Harness break near the evaporator bulkhead penetration
    • Connector at the controller or sensor pigtail corroded
    • Sensor failed open or shorted internally

    Checks

    1. 1Look at the sensor in the return air stream and its lead for physical damage
    2. 2Read sensor resistance at the unit connector and compare with the other air sensor at the same temperature
    3. 3Ohm the wires to the controller end for an open, then to ground for a short
    4. 4Swap in a known-good sensor temporarily to confirm whether the fault follows the sensor
    5. 5Compare the controller sensor readout with a reference thermometer in the airstream
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 04Check discharge air sensor

    The discharge air sensor, which sits in the cold air leaving the evaporator, gives a reading outside its normal range.· Other
    Check soon

    Causes

    • Discharge sensor lead rubbed through against the coil frame or fan housing
    • Frost or water in the probe connector
    • Sensor element failed open or short
    • Pin loose in the main harness plug

    Checks

    1. 1Inspect the discharge sensor probe and lead at the evaporator outlet for rubbing or ice damage
    2. 2Measure sensor resistance at the harness plug and check it changes when you warm the probe by hand
    3. 3Check continuity from the plug to the controller pin for both wires
    4. 4Test each harness wire to ground with the plug off to rule out a short to the frame
    5. 5Compare with the return sensor in a stable box, since they should differ only by the coil load
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 05Check ambient temperature sensor

    The ambient (outside air) sensor is reading out of range.· Other
    Check soon

    Causes

    • Ambient sensor mounted in the condenser airflow with a damaged lead
    • Connector at the sensor full of road salt or water
    • Sensor open or shorted
    • Wire pinched at the frame where it passes through

    Checks

    1. 1Locate the ambient sensor at the condenser inlet and inspect the lead and plug
    2. 2Take its resistance and match it to the current outside temperature using the sensor chart in the manual
    3. 3Check the harness wires for continuity back to the controller
    4. 4Look for shorts to ground along the lead where it contacts the frame
    5. 5Replace the sensor if the reading is fixed regardless of temperature
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 08Unit running on coil sensor

    The unit has lost trust in its air sensors and is controlling temperature from the evaporator coil sensor instead.· Other
    Check soon

    Causes

    • Return air sensor open or shorted
    • Discharge sensor fault feeding the fallback
    • Harness break between evaporator sensors and controller

    Checks

    1. 1Read the active sensor alarms alongside 08, usually 03 or 04, and fix those first
    2. 2Check the air sensor resistances against the coil sensor at the same temperature
    3. 3Inspect the evaporator sensor harness for damage
    4. 4Clear alarms and confirm the unit returns to normal sensor control
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 11Controlling on alternate sensor

    One of the control sensors has failed, so the unit is regulating box temperature from an alternate sensor.· Other
    Check soon

    Causes

    • Primary air sensor open or shorted
    • Damaged sensor harness near the evaporator
    • Sensor plug corroded or pin pushed out

    Checks

    1. 1Read the sensor alarms active together with 11 to learn which probe is gone
    2. 2Measure the faulty sensor resistance at the plug and compare with its partner
    3. 3Inspect the lead for damage along its full route to the controller
    4. 4Replace the sensor or repair the wiring, then clear alarms and watch which sensor the unit controls on
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 12Sensor or digital input shutdown

    A required sensor or digital input has failed and the controller considers the unit unsafe or unable to control, so it has shut itself down.· Other
    Stop now

    Causes

    • Open or shorted sensor lead that the controller needs for operation
    • Failed digital input such as a safety switch
    • Loose connector at the controller

    Checks

    1. 1Look for other alarms stored with 12, which usually name the failed input
    2. 2Check each sensor and switch circuit resistance against the diagnostic manual
    3. 3Inspect the harness plugs for water or corrosion
    4. 4Reconnect, clear alarms, and attempt a restart while watching the alarm list
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 13Sensor check

    The controller failed a sensor grading check, meaning a sensor reading does not agree with the others in the way it should after a pretrip or at start-up.· Other
    Check soon

    Causes

    • A temperature sensor drifted out of tolerance
    • Sensor probe not seated in its holder
    • Sensor lead damaged

    Checks

    1. 1Run the pretrip test and look at which sensor the controller points to
    2. 2Compare sensor temperatures at stable conditions to find the odd one
    3. 3Check each probe is fully seated in its holder
    4. 4Check the lead for damage and re-grade or replace the sensor
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 47Remote sensor shutdown

    A remote sensor (such as a trailer or compartment sensor) that the unit relies on has failed and the unit has shut down.· Other
    Stop now

    Causes

    • Remote sensor cable cut
    • Plug corroded
    • Sensor failed

    Checks

    1. 1Check the remote sensor cable along its full route
    2. 2Measure the remote sensor resistance at its plug
    3. 3Inspect the remote sensor plug for water or corrosion at its pins
    4. 4Replace the remote sensor and retest to confirm the shutdown clears
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 49Spare sensor 1 check

    The controller sees a fault on the spare temperature input 1, which is not used for control on most units.· Other
    Info

    Causes

    • Spare sensor fitted but not connected or configured
    • Open or shorted spare sensor lead

    Checks

    1. 1Check whether a spare sensor is actually fitted and configured in the controller
    2. 2Unplug the spare sensor and read its resistance at the pins
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 80Check compressor temperature sensor

    The compressor discharge temperature sensor reading is out of its valid range, so the controller cannot watch for compressor overheating.· Real condition
    Check soon

    Causes

    • Sensor lead damaged near the compressor head
    • Sensor failed open or short
    • Connector corroded or wet

    Checks

    1. 1Locate the sensor on the compressor discharge and inspect it and its lead
    2. 2Measure sensor resistance and compare with the manual chart
    3. 3Check the continuity of the wires to the controller
    4. 4Replace the sensor if its value is stuck or does not follow compressor warm-up
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 81High compressor temperature

    The compressor discharge temperature has risen above the warning limit.· Other
    Check soon

    Causes

    • Low refrigerant charge causing hot gas
    • Dirty condenser
    • Restricted suction or an expansion valve starving
    • Compressor internal wear

    Checks

    1. 1Check refrigerant charge through the sight glass
    2. 2Clean the condenser coil with a soft brush and low-pressure water or air
    3. 3Check the suction pressure and superheat to see whether the compressor is being starved
    4. 4Check the compressor sensor against an infrared reading
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 82High compressor temperature shutdown

    The compressor discharge temperature reached the shutdown limit and the controller stopped the unit to prevent damage to the compressor.· Other
    Stop now

    Causes

    • Low charge or loss of refrigerant cooling the compressor
    • Condenser airflow blocked
    • Compressor internal failure
    • Liquid injection or economizer valve not working

    Checks

    1. 1Check for refrigerant leaks and recover or recharge as needed
    2. 2Clean the condenser and check the condenser fan and its drive for correct speed
    3. 3Check the liquid injection or economizer valves operate
    4. 4Check the compressor oil level and the oil condition for burnt smell or metal
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 92Sensor grades not set

    The temperature sensor grading values have not been set or are missing after a controller or sensor replacement.· Other
    Info

    Causes

    • New controller installed without grading
    • Software reset cleared grades
    • Sensor swap not recorded

    Checks

    1. 1Run the sensor grading procedure in the service menu
    2. 2Verify the sensors are connected and giving readings before grading them
    3. 3Clear the alarm after grading and confirm it does not come back at start-up
    4. 4Compare the readings with a reference thermometer
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 97Failed remote return air sensor (CR)

    On CR units, the remote return air sensor has failed or is out of range, so the controller has lost the return temperature it uses for control.· Other
    Check soon

    Causes

    • Remote sensor cable cut
    • Plug corroded
    • Sensor failed

    Checks

    1. 1Check the remote sensor cable along its length for cuts, kinks or crushed sections
    2. 2Measure the remote sensor resistance and compare it with the manual sensor chart
    3. 3Inspect the remote sensor plug for water or corrosion at the pins
    4. 4Replace the remote sensor if it reads open or shorted at the plug
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 150Sensor out of range low

    A sensor signal is below the lowest value the controller accepts.· Shorted low
    Check soon

    Causes

    • Sensor wire shorted to ground or the frame
    • Sensor element failed shorted
    • Connector wet and leaking to ground

    Checks

    1. 1Disconnect the sensor and see if the alarm changes to out of range high, which proves the sensor and wiring
    2. 2Measure the sensor resistance and compare it with the sensor chart
    3. 3Check each wire to ground with the plug off for a short
    4. 4Inspect the lead where it passes sharp edges and frame holes
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.

    Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.

  • Thermo King 151Sensor out of range high

    A sensor signal is above the highest value the controller accepts.· Open circuit
    Check soon

    Causes

    • Sensor wire broken or unplugged
    • Pin backed out of the connector
    • Sensor element failed open

    Checks

    1. 1Wiggle the sensor lead and plug while watching the reading for jumps
    2. 2Measure the sensor resistance, where infinite means an open element
    3. 3Check continuity of both wires between the sensor plug and controller
    4. 4Look for a pin pushed back inside the connector
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.

    Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.

  • Thermo King 203Check display return air sensor

    The return air temperature shown on the remote display is out of range, so the display value is wrong even if the control sensor reads normally.· Other
    Check soon

    Causes

    • Display return sensor lead crushed by a door or panel
    • Probe plug corroded from condensation
    • Sensor element open

    Checks

    1. 1Compare the display return air figure with the controller return air reading
    2. 2Look along the display sensor lead for crush marks at doors and panel edges
    3. 3Measure the probe resistance against the sensor chart and compare with ambient
    4. 4Clear it in the Maintenance or Guarded Access menu once repaired, since the Alarms menu will not clear it
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 204Check display discharge air sensor

    The discharge air reading shown on the display is out of range, which points at the display discharge sensor channel and not at the unit's control sensor itself.· Other
    Check soon

    Causes

    • Display discharge sensor wire pinched at the evaporator
    • Connector fault at the display sensor
    • Sensor element failed

    Checks

    1. 1Compare the display discharge reading with the controller discharge reading
    2. 2Inspect the display sensor lead and connector for damage
    3. 3Measure the sensor resistance against the chart
    4. 4Clear it in the Maintenance or Guarded Access menu once repaired
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

Shared checks

Checks, in order

  1. 1Find the named probe and trace its lead to the unit harness for damage and pinched spots
  2. 2Read the active alarm list first and find which probe triggered the fall-back
  3. 3Compare the compressor temperature on the display with an infrared reading on the head
  4. 4Unplug the probe and read its resistance at the pins; an open or near-zero reading means the probe is dead
  5. 5Check the probe lead and plug of that sensor before replacing anything
  6. 6Clean the condenser coil and check that the condenser fan runs
  7. 7Compare the reading with a known-good probe at the same temperature, since probes of one type should match

Causes

  • Probe lead chafed or cut where it leaves the evaporator or the air chute
  • Failed probe whose substitute is also marginal
  • Low refrigerant charge or a restricted line starving the compressor of cooling
  • Sensor plug at the controller corroded or pushed back

When to stop

You'll notice: The alarm number shows on the display and the unit may control on another sensor or run defrost on a timer, so box temperature drifts or the coil ices up.

Let the engine cool before opening the cooling system; a hot cap releases scalding coolant. Running on with an overheat warning risks a head gasket or seized engine.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.

Machine down?

Get a replacement machine or a technician - suppliers in the UAE contact you.

Post a request
EquipmentsFinder

Need equipment? Have equipment?

Buyers post one request and get quotes from suppliers. Suppliers list free and reach active demand.