Skyjack · GP102 module LED flash codes

Skyjack Tilt, overload, armguard and elevation switch codes fault codes

This page covers the GP102 cut-outs and the switches behind them: tilt, overload and height cut-outs, the armguard stop, and the elevation switch in both running faults and calibration F-codes. The GP102 module watches the tilt sensor, the load pressure transducer and the height sensor.

More about these parts

The armguard (scissor-arm guard) input tells the GP102 that something is touching the guard. The elevation switch on P2-10 tells the GP102 whether the platform is lowered or raised, and the module uses it to allow drive, set limits and cross-check the height sensor.

FaultInfo1-1Skyjack · Tilt, overload, armguard and elevation switch codes
Code shows hereFAULT1-1

Where this code shows

Find the LED on the GP102 module (older SJIII scissors) or the display and keypad in the hydraulic tray (Skycoded machines).

What do these codes mean?

Skyjack codes 1-1 to F47 are all about the tilt, overload, armguard and elevation switch codes. Most are part or controller faults; none needs an immediate stop. Start with this check: lower the platform fully and look at the ground under the machine before touching anything.

How urgent are they?

None of the 17 codes here means stop now; 11 can wait until the shift ends, but find the cause before the next one; 6 are information only.

  • Check soon11
  • Info6

What should I check first?

Lower the platform fully and look at the ground under the machine before touching anything

Shared checks

17 of 17

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Skyjack 1-1Vehicle tilted

    The tilt sensor inside the GP102 module sees the machine standing on a slope steeper than its cut-out angle.· Other
    Info

    Causes

    • Machine parked or driven on a slope or uneven ground
    • One wheel or a pothole bar sitting on a kerb, ramp edge or debris
    • GP102 module loose or mounted crooked on its bracket, so it reads a false angle
    • Tilt sensor reading wrong after the module was replaced

    Checks

    1. 1Lower the platform completely first, then look at what the machine is standing on
    2. 2Move the machine onto firm level ground and see whether the flash code clears by itself
    3. 3Check the GP102 module mounting bolts are tight and the module sits flat on its bracket
    4. 4Put a spirit level on the chassis next to the module to confirm the chassis really is level
    5. 5If the code stays on level ground, read the LED again for 7-1 (bad tilt sensor) before replacing anything
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Skyjack 1-2Vehicle overloaded

    The pressure transducer on the lift cylinder tells the GP102 module the platform load is above the rated limit.· Real condition
    Info

    Causes

    • More people, tools or material on the platform than the rated capacity
    • Platform pressed against a beam or ceiling, which adds to the cylinder pressure
    • Lift cylinder pressure transducer reading high or out of calibration
    • Load calibration lost after a battery or module change

    Checks

    1. 1Take the load off and compare what was on the platform with the capacity plate
    2. 2Look for the platform touching an overhead structure and use the emergency lowering if it is trapped
    3. 3With the platform empty, measure the transducer signal at P4-2; it should sit between 0.5 V and 4.5 V and not at the top of the range
    4. 4Check the transducer connector and cable at the lift cylinder for oil, water or damage
    5. 5If an empty platform still reads overloaded, repeat the load calibration (see 6-2)
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Skyjack 1-3Armguard active (lift and drive stopped)

    The arm-guard input is blocking movement and the module is reporting that as the reason.· Other
    Info

    Causes

    • Scissor arm guard tripped by an object or a person
    • Guard switch stuck, bent or out of adjustment
    • Wire from the guard switch pinched or open at the module plug
    • Debris or a tool jammed under the scissor stack

    Checks

    1. 1Walk round the scissor stack and look for anything touching or resting on the guard
    2. 2Trip the guard by hand and listen for the switch click; look for a bent bracket or seized lever
    3. 3Check the switch connector for a pushed-back pin or corrosion
    4. 4Compare with 2-3, which reports the same guard at the moment a function is being driven
    5. 5After freeing it, cycle the controls and confirm the LED returns to steady on
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Skyjack 1-4Too high, drive prevented

    The height transducer shows the platform above the height where driving is allowed.· Real condition
    Info

    Causes

    • Platform raised above the drive-height cut-out, which is normal behaviour
    • Height transducer reading high so the module thinks the platform is higher than it is
    • Cable damage between the height sensor and plug P4
    • Height calibration missing after the module or sensor was replaced

    Checks

    1. 1Lower the platform fully and see whether drive returns; if it does, the machine is behaving normally
    2. 2With the platform down, measure the height signal at P4-3; the manual gives 0.4 V to 4.6 V and it should change as the platform rises
    3. 3Check the P4 plug for corrosion and follow the cable for chafing near the scissor pivots
    4. 4Raise slowly while watching P4-3; a jump or dropout points at the sensor or its wire
    5. 5Repeat the height calibration if the sensor or module was changed (see 6-1)
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Skyjack 1-5Too high, lift up prevented

    The module is refusing further lift-up because the height or the load and height combination has reached the allowed limit.· Real condition
    Info

    Causes

    • Platform genuinely at its maximum height
    • Height transducer reading high and ending lift early
    • Overload or tilt condition active at the same time
    • Wrong or stale height calibration

    Checks

    1. 1Check the platform is not already at full height or touching a ceiling
    2. 2Read the height signal at P4-3 at a known platform height; it should stay between 0.4 V and 4.6 V
    3. 3Look for an active overload (1-2) or tilt (1-1) code that is also blocking lift
    4. 4Inspect the P4 cable and connector at the height sensor for damage
    5. 5Recalibrate the height sensor if the readings disagree with the real height
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Skyjack 2-1Elevation switch shifted?

    The module sees the elevation switch change state at a platform position where it should not.· Other
    Check soon

    Causes

    • Elevation switch loose on its bracket so it has moved out of position
    • Operating arm or cam bent or worn
    • Switch contacts dirty or intermittent
    • Wire rubbing at the scissor arm pivot

    Checks

    1. 1Raise and lower the platform slowly and watch the switch operate; it must change state at the same point every time
    2. 2Check the bracket bolts are tight and the switch has not slid along its slot
    3. 3Look at the actuating arm for bending or wear marks
    4. 4Test the switch across its terminals in both positions for a clean open and closed reading
    5. 5Check the wire at the pivot for chafing, then cycle power and watch whether the code returns
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Skyjack 2-2Elevation switch stuck?

    The module sees the elevation switch staying in one state while the platform moves.· Other
    Check soon

    Causes

    • Switch seized in the open or closed position
    • Actuator not reaching the switch because of damage or wrong position
    • Open or shorted wire on the switch circuit
    • Dirt or hydraulic oil packed around the switch

    Checks

    1. 1With the platform fully down note the switch state, then raise a little and see if it changes
    2. 2Push the actuator by hand and listen or feel for a click
    3. 3Clean around the switch and check the actuator moves freely on its pivot
    4. 4Check continuity of the switch wires with the plug disconnected to find a break
    5. 5Replace the switch if it cannot follow the arm, then raise and lower to clear the code
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Skyjack 2-3Armguard active (one-off flash)

    This is the arm-guard reason reported while a function is being used.· Other
    Info

    Causes

    • Operator or object tripped the scissor arm guard
    • Guard switch sticking and releasing
    • Loose connector giving a short pulse on the guard input
    • Debris under the arm guard

    Checks

    1. 1Clear anything away from the arm guard and confirm the machine moves again
    2. 2Trip the guard by hand a few times and check the switch returns freely each time
    3. 3Wiggle the guard switch connector with the machine powered; a flash code appearing means a loose pin
    4. 4Compare against 1-3 to tell a standing guard problem from a one-off trip
    5. 5If it flashes without being touched, look for an intermittent short in the switch wire
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Skyjack F06Calibration F06: elevation switch closed at start

    The elevation switch at P2-10 was closed at the start of calibration after the operator confirmed that the platform is down.· Part or controller
    Check soon

    Causes

    • Elevation switch stuck or misadjusted
    • Wire to the switch shorted

    Checks

    1. 1Check the platform is really down and the switch is open
    2. 2Check the elevation switch wiring
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F08Calibration F08: elevation switch closed at top

    The elevation switch at P2-10 was closed at the end of calibration, when the platform should be fully raised.· Part or controller
    Check soon

    Causes

    • UP switch accidentally released near the start of the lift
    • Elevation switch wiring fault

    Checks

    1. 1Repeat the lift without letting go of UP
    2. 2Check the elevation switch wiring
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F15Calibration F15: elevation switch closed at bottom

    The elevation switch at P2-10 was closed when the platform had been fully lowered at the end of the calibration.· Part or controller
    Check soon

    Causes

    • DOWN switch released before the platform was fully lowered
    • Elevation switch fault

    Checks

    1. 1Lower the platform fully and check the switch
    2. 2Check the elevation switch wiring
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F16Calibration F16: elevation switch opened too low

    The elevation switch opened during lift at too low a height, below 5 percent.· Part or controller
    Check soon

    Causes

    • Elevation switch set too low
    • Switch cam out of position

    Checks

    1. 1Check the ElevUp value in CALIBRATIONS, HEIGHT CALS
    2. 2Set the switch to the manufacturer specification and recalibrate the load
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F17Calibration F17: elevation switch opened too high

    The elevation switch opened during lift at too high a height, above 25 percent of the travel.· Part or controller
    Check soon

    Causes

    • Elevation switch set too high
    • Switch cam out of position

    Checks

    1. 1Check the ElevUp value in CALIBRATIONS, HEIGHT CALS
    2. 2Set the switch to the manufacturer specification and recalibrate the load
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F18Calibration F18: elevation switch closed too low

    The elevation switch closed during lowering at too low a height, below 5 percent of the travel.· Part or controller
    Check soon

    Causes

    • Elevation switch set too low
    • Switch cam out of position

    Checks

    1. 1Check the ElevDown value in CALIBRATIONS, HEIGHT CALS
    2. 2Set the switch to the manufacturer specification and recalibrate the load
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F19Calibration F19: elevation switch closed too high

    The elevation switch closed during lowering at too high a height, above 25 percent of the travel.· Part or controller
    Check soon

    Causes

    • Elevation switch set too high
    • Switch cam out of position

    Checks

    1. 1Check the height values in CALIBRATIONS, HEIGHT CALS
    2. 2Set the switch to the manufacturer specification and recalibrate the load
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F46Calibration F46: elevation switch opened twice

    The elevation switch opened more than once during the lifting part of the calibration, so the switch is bouncing or unreliable.· Part or controller
    Check soon

    Causes

    • Loose or worn elevation switch
    • Intermittent switch wiring

    Checks

    1. 1Check the switch mounting and cam
    2. 2Check the wiring for intermittent contact
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Skyjack F47Calibration F47: elevation switch closed twice

    The elevation switch closed more than once during the lowering part of the calibration, so the switch is bouncing or unreliable.· Part or controller
    Check soon

    Causes

    • Loose or worn elevation switch
    • Intermittent switch wiring

    Checks

    1. 1Check the switch mounting and cam
    2. 2Check the wiring for intermittent contact
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

Shared checks

Checks, in order

  1. 1Lower the platform fully and look at the ground under the machine before touching anything
  2. 2Walk round the machine and look for anything resting on or against the guard
  3. 3Raise and lower the platform and watch the switch open and close at the same point every time
  4. 4Take excess load off the platform and see whether the flash code clears by itself
  5. 5Operate the guard switch by hand, listen for the click and check the bracket is not bent
  6. 6Check the switch mounting, cam and bracket for movement or damage
  7. 7Move the machine to firm level ground and cycle the key switch

Causes

  • Machine standing on a slope or on one raised wheel
  • Object or person touching the guard
  • Elevation switch cam or bracket moved out of adjustment
  • Too much weight or a badly placed load on the platform

Most codes here: part or controller (9 of 17)

Check power and ground at the module connector with the key on, then its fuses.

When to stop

You'll notice: A function stops working and the module LED repeats a short flash pattern.

Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.