JLG · Outputs (valves and coils)
JLG Telescope and jib lift valves fault codes
The telescope valves are the two solenoid coils that extend and retract the boom. The jib lift valves are the two coils that raise and lower the jib on the boom end, driven through the ground module and the platform valve block, so a jib coil may appear under two numbers.
More about these partsLess
The module watches each output for a short or open circuit.
Where this code shows
Turn the key on and watch the fault lamp or platform display.
What do these codes mean?
JLG codes 3415 to 33190 are all about the telescope and jib lift valves. The most common failure type is shorted high (6 of 18); none needs an immediate stop. Start with this check: read the Help message to see which coil and direction is named.
How urgent are they?
None of the 18 codes here means stop now; all 18 can wait until the shift ends, but find the cause before the next one.
- Check soon18
What should I check first?
Read the Help message to see which coil and direction is named
Shared checks18 of 18
Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet
Jib Lift Up Valve6 codes
JLG 3415Jib Lift Up Valve: Open circuit
The controller drives the jib lift up valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Open circuitOpen circuitCheck soonCauses
- Jib lift up valve solenoid coil burnt out or open
- Jib up coil open, so the jib will not rise and stays where it is
- Lead stretched or kinked until it broke along the boom and out to the jib pivot, where the cable is bent on every jib movement
Checks
- 1Ohm the solenoid coil on the boom valve block with the plug off and compare with a matching good coil
- 2Test both wires with the plug off and flex them along the boom and out to the jib pivot, where the cable is bent on every jib movement to catch a hidden break
- 3Select jib up at the platform and listen for the click at the jib valve, then watch the jib rise; the analyzer should show the module sending the command
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 3416Jib Lift Up Valve: Short to battery
The controller reads battery voltage on the jib lift up valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Shorted highShorted highCheck soonCauses
- Insulation worn between the signal and a supply feed
- Jib up wire touching a feed at the boom end so the jib rises by itself
- Melted insulation along the boom and out to the jib pivot, where the cable is bent on every jib movement
Checks
- 1With the jib lift up valve plug off on the boom valve block and the key on, measure the output wire to ground; any voltage means a short to supply
- 2Trace the wire alongside any supply wire and look for a touch point along the boom and out to the jib pivot, where the cable is bent on every jib movement
- 3Watch the analyzer output as you select jib up at the platform and listen for the click at the jib valve, then watch the jib rise
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
JLG 3417Jib Lift Up Valve: Short to ground
The controller sees the jib lift up valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Shorted lowShorted lowCheck soonCauses
- Coil winding rubbing its own case until it earths
- Jib up coil shorted at the boom end where knocks and sun have cracked the lead
- Signal wire rubbed bare on metal along the boom and out to the jib pivot, where the cable is bent on every jib movement
Checks
- 1Unplug the jib lift up valve on the boom valve block; if the code clears the solenoid coil is the short, if not the wiring or module is
- 2Meter the signal wire to the frame, flexing it along the boom and out to the jib pivot, where the cable is bent on every jib movement for a reading that comes and goes
- 3With the analyzer open, select jib up at the platform and listen for the click at the jib valve, then watch the jib rise and watch the output state
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
JLG 33100Jib Lift Up Valve: Short to ground
The controller sees the jib lift up valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it.· Shorted lowShorted lowCheck soonCauses
- Coil winding rubbing its own case until it earths
- Jib up coil shorted at the boom end where knocks and sun have cracked the lead
- Signal wire rubbed bare on metal along the boom and out to the jib pivot, where the cable is bent on every jib movement
- Wet or corroded plug, since the jib up plug is at the boom end, exposed to sun, wash water and knocks from the cage
Checks
- 1Unplug the jib lift up valve on the boom valve block; if the code clears the solenoid coil is the short, if not the wiring or module is
- 2Meter the signal wire to the frame, flexing it along the boom and out to the jib pivot, where the cable is bent on every jib movement for a reading that comes and goes
- 3With the analyzer open, select jib up at the platform and listen for the click at the jib valve, then watch the jib rise and watch the output state
- 4Check the jib up lead at the boom end for a cracked or crushed section
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
JLG 33101Jib Lift Up Valve: Open circuit
The controller drives the jib lift up valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it.· Open circuitOpen circuitCheck soonCauses
- Jib lift up valve solenoid coil burnt out or open
- Jib up coil open, so the jib will not rise and stays where it is
- Lead stretched or kinked until it broke along the boom and out to the jib pivot, where the cable is bent on every jib movement
- Terminal worn loose in its housing (the jib up plug is at the boom end, exposed to sun, wash water and knocks from the cage)
Checks
- 1Ohm the solenoid coil on the boom valve block with the plug off and compare with a matching good coil
- 2Test both wires with the plug off and flex them along the boom and out to the jib pivot, where the cable is bent on every jib movement to catch a hidden break
- 3Select jib up at the platform and listen for the click at the jib valve, then watch the jib rise; the analyzer should show the module sending the command
- 4Try jib down: if it works the jib circuit is alive and only the up coil is open
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 33102Jib Lift Up Valve: Short to battery
The controller reads battery voltage on the jib lift up valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it.· Shorted highShorted highCheck soonCauses
- Insulation worn between the signal and a supply feed
- Jib up wire touching a feed at the boom end so the jib rises by itself
- Melted insulation along the boom and out to the jib pivot, where the cable is bent on every jib movement
- Wet plug bridging the signal pin to supply, since the jib up plug is at the boom end, exposed to sun, wash water and knocks from the cage
Checks
- 1With the jib lift up valve plug off on the boom valve block and the key on, measure the output wire to ground; any voltage means a short to supply
- 2Trace the wire alongside any supply wire and look for a touch point along the boom and out to the jib pivot, where the cable is bent on every jib movement
- 3Watch the analyzer output as you select jib up at the platform and listen for the click at the jib valve, then watch the jib rise
- 4Watch the jib with no switch pressed; any movement means the output is held on
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Jib Lift Down Valve6 codes
JLG 3418Jib Lift Down Valve: Open circuit
The controller drives the jib lift down valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Open circuitOpen circuitCheck soonCauses
- Jib lift down valve solenoid coil burnt out or open
- Jib down coil open, so the jib will not come down and the platform cannot tuck under obstacles
- Wire broken inside its insulation at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
Checks
- 1Unplug the jib lift down valve on the boom valve block and measure across its two pins; an open reading means a dead solenoid coil
- 2Test between the module pin and the plug section by section, beginning at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- 3Select jib down, listen for the click, and watch whether the jib comes down under control; the analyzer should show the module sending the command
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 3419Jib Lift Down Valve: Short to battery
The controller reads battery voltage on the jib lift down valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Shorted highShorted highCheck soonCauses
- Insulation worn between the signal and a supply feed
- Jib down wire touching a feed so the jib drops by itself
- Supply wire pinched against the output wire at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
Checks
- 1With the load off on the boom valve block and the key on, any reading on the output wire is the short
- 2Feel along the harness at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered for scuffed, hard or discoloured insulation
- 3Retest after the repair: select jib down, listen for the click, and watch whether the jib comes down under control
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
JLG 3420Jib Lift Down Valve: Short to ground
The controller sees the jib lift down valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it. This number belongs to the platform valve block driver series (flash code 3-4), which lists the same valve separately from the ground module codes.· Shorted lowShorted lowCheck soonCauses
- Coil winding rubbing its own case until it earths
- Jib down coil shorted by a lead pulled tight at the pivot clamp
- Signal wire rubbed bare on metal at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
Checks
- 1Disconnect the load on the boom valve block; the code staying means a harness or module fault
- 2Test the output wire to the chassis with the connector open; any path is the short, most likely at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- 3With the analyzer open, select jib down, listen for the click, and watch whether the jib comes down under control and watch the output state
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
JLG 33103Jib Lift Down Valve: Short to ground
The controller sees the jib lift down valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it.· Shorted lowShorted lowCheck soonCauses
- Coil winding rubbing its own case until it earths
- Jib down coil shorted by a lead pulled tight at the pivot clamp
- Signal wire rubbed bare on metal at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- Wet or corroded plug, since the jib down connector is on the boom end block, where the cable is often snagged by the cage
Checks
- 1Disconnect the load on the boom valve block; the code staying means a harness or module fault
- 2Test the output wire to the chassis with the connector open; any path is the short, most likely at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- 3With the analyzer open, select jib down, listen for the click, and watch whether the jib comes down under control and watch the output state
- 4Check the clamp at the jib pivot for a lead being crushed or pulled
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
JLG 33104Jib Lift Down Valve: Open circuit
The controller drives the jib lift down valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it.· Open circuitOpen circuitCheck soonCauses
- Jib lift down valve solenoid coil burnt out or open
- Jib down coil open, so the jib will not come down and the platform cannot tuck under obstacles
- Wire broken inside its insulation at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- Pin backed out or loose in the connector, because the jib down connector is on the boom end block, where the cable is often snagged by the cage
Checks
- 1Unplug the jib lift down valve on the boom valve block and measure across its two pins; an open reading means a dead solenoid coil
- 2Test between the module pin and the plug section by section, beginning at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- 3Select jib down, listen for the click, and watch whether the jib comes down under control; the analyzer should show the module sending the command
- 4Try jib up: if it works the circuit is alive and only the down coil is open
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 33105Jib Lift Down Valve: Short to battery
The controller reads battery voltage on the jib lift down valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it.· Shorted highShorted highCheck soonCauses
- Insulation worn between the signal and a supply feed
- Jib down wire touching a feed so the jib drops by itself
- Supply wire pinched against the output wire at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered
- Corrosion between pins in the plug (the jib down connector is on the boom end block, where the cable is often snagged by the cage)
Checks
- 1With the load off on the boom valve block and the key on, any reading on the output wire is the short
- 2Feel along the harness at the jib pivot clamp, where the jib wires are pulled tight when the jib is lowered for scuffed, hard or discoloured insulation
- 3Retest after the repair: select jib down, listen for the click, and watch whether the jib comes down under control
- 4Hold the jib clear of people and see whether it sinks with no switch pressed
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Telescope In Valve3 codes
JLG 33120Telescope In Valve: Short to battery
The controller reads battery voltage on the telescope in valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it.· Shorted highShorted highCheck soonCauses
- Output wire touching a battery-fed wire where two harness legs cross
- Telescope in wire touching a feed along the boom so the boom tries to retract by itself
- Damaged sheath along the boom, where the cable is pulled and released by the telescoping section, exposing the wire to a live one
- Corrosion between pins in the plug (the telescope in plug is on the boom bank, near moving hoses that rub it)
Checks
- 1With the load off on the boom valve bank and the key on, any reading on the output wire is the short
- 2Trace the wire alongside any supply wire and look for a touch point along the boom, where the cable is pulled and released by the telescoping section
- 3Watch the analyzer output as you select telescope in at the platform and listen for the solenoid click on the boom bank, then watch the boom retract
- 4Hold the platform clear and watch whether the boom creeps in with no switch pressed
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
JLG 33189Telescope In Valve: Open circuit
The controller drives the telescope in valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it.· Open circuitOpen circuitCheck soonCauses
- Winding burnt through at one end so the coil reads open
- Telescope in coil open, so the boom will not retract and cannot be stowed
- Lead stretched or kinked until it broke along the boom, where the cable is pulled and released by the telescoping section
- Contact fretting in the plug, which is likely because the telescope in plug is on the boom bank, near moving hoses that rub it
Checks
- 1Meter the solenoid coil on the boom valve bank for an open reading
- 2Meter the wires end to end while someone moves the harness along the boom, where the cable is pulled and released by the telescoping section
- 3With the analyzer open, select telescope in at the platform and listen for the solenoid click on the boom bank, then watch the boom retract; if the output switches but nothing happens, the solenoid coil is open
- 4Try telescope out: if it works the circuit is alive and only the in coil is open
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 33190Telescope In Valve: Short to ground
The controller sees the telescope in valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it.· Shorted lowShorted lowCheck soonCauses
- Coil winding rubbing its own case until it earths
- Telescope in coil shorted where hoses have rubbed the cable on the boom bank
- Signal wire rubbed bare on metal along the boom, where the cable is pulled and released by the telescoping section
- Wet or corroded plug, since the telescope in plug is on the boom bank, near moving hoses that rub it
Checks
- 1Separate the connector on the boom valve bank and see whether the code goes with the load
- 2Meter between the signal pin and chassis with the plug apart; a reading shows the earth path, probably along the boom, where the cable is pulled and released by the telescoping section
- 3With the analyzer open, select telescope in at the platform and listen for the solenoid click on the boom bank, then watch the boom retract and watch the output state
- 4Check the boom bank for hoses rubbing the telescope in lead
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Telescope Out Valve3 codes
JLG 33123Telescope Out Valve: Short to battery
The controller reads battery voltage on the telescope out valve output while it is commanded off, so the circuit is shorted to battery. EMS must be recycled to clear it.· Shorted highShorted highCheck soonCauses
- Two harness legs bundled so tightly that a worn spot joins them
- Telescope out wire touching a feed in the boom cable guide so the boom may extend by itself
- Melted insulation where the harness is paid out as the boom extends and can snag in the cable guide
- Corrosion between pins in the plug (the telescope out connector sits on the boom block, where hoses can chafe the cable)
Checks
- 1With the load off on the boom valve bank and the key on, any reading on the output wire is the short
- 2Inspect the harness for bare spots, burnt insulation and melted clamps, especially where the harness is paid out as the boom extends and can snag in the cable guide
- 3Retest after the repair: select telescope out, listen for the click and see whether the boom extends
- 4Watch the boom with no switch pressed; any extension means the output is held on
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
JLG 33186Telescope Out Valve: Open circuit
The controller drives the telescope out valve output but feedback shows an open circuit (feedback reads high while the output is off). That function will not work; EMS must be recycled to clear it.· Open circuitOpen circuitCheck soonCauses
- Open winding in the coil
- Telescope out coil open, so the boom will not extend and reach is limited
- Wire work-hardened and snapped inside its sheath where the harness is paid out as the boom extends and can snag in the cable guide
- Terminal worn loose in its housing (the telescope out connector sits on the boom block, where hoses can chafe the cable)
Checks
- 1Ohm the solenoid coil on the boom valve bank with the plug off and compare with a matching good coil
- 2Check continuity from the module output pin to the plug, wiggling the wire as you test, starting where the harness is paid out as the boom extends and can snag in the cable guide
- 3With the analyzer open, select telescope out, listen for the click and see whether the boom extends; if the output switches but nothing happens, the solenoid coil is open
- 4Try telescope in: if it works the circuit is alive and only the out coil is open
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
JLG 33188Telescope Out Valve: Short to ground
The controller sees the telescope out valve output pulled low while it is commanded on, so the circuit is shorted to ground. EMS must be recycled to clear it.· Shorted lowShorted lowCheck soonCauses
- Coil insulation failed, leaking to the body
- Telescope out coil shorted where the cable is paid out through the guide and has been cut
- Wire chafed through to the frame where the harness is paid out as the boom extends and can snag in the cable guide
- Dirt and water bridging a pin to ground; the telescope out connector sits on the boom block, where hoses can chafe the cable
Checks
- 1Separate the connector on the boom valve bank and see whether the code goes with the load
- 2With the plug off, check the signal wire to the frame (it should be open), starting where the harness is paid out as the boom extends and can snag in the cable guide
- 3Select telescope out, listen for the click and see whether the boom extends; the analyzer output should go to supply, not stay at zero
- 4Run the cable through the guide by hand while metering the out lead to the frame
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure resistance from the signal wire to ground and to the machine frame.
Good: Open circuit (OL) to ground. A low reading means chafed insulation touching metal.
Shared checks
Checks, in order
- 1Read the Help message to see which coil and direction is named
- 2Command that direction and listen for the coil click on the valve bank
- 3Unplug the coil: a changed code points at the coil, an unchanged one at the harness or module
- 4Ohm the coil and look along the boom harness for rub marks
- 5Retest both directions after the repair and note exactly what the analyzer shows
Causes
- Coil failed from heat, water or age
- Harness chafed where it runs along the boom
- Loose or corroded coil plug
- Output driver in the module damaged
Most common here: shorted high (6 of 18)
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
When to stop
You'll notice: The boom will not extend or retract, or the jib will not move up or down, or one of them creeps on its own, while other functions still work.
Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.
Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.
Related on Equipments Finder
Sources
Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.