Thermo King · Refrigeration system (SR-2/SR-3/SR-4)
Thermo King Refrigeration pressures, scroll compressor limits, modulation and drive fault codes
This page covers the refrigeration circuit pressures and limits: high-side pressure and cutout, suction-side pressure, the scroll compressor operating limits, capacity modulation and the compressor drive belts and clutch. The discharge side of the refrigeration circuit is watched by a pressure sensor and a high pressure cutout switch.
More about these partsLess
A suction pressure sensor and a low pressure switch watch the low side of the circuit. On units with a scroll compressor the controller watches the suction pressure, discharge pressure, pressure ratio and discharge superheat, and the economizer pressure. The compressor capacity is adjusted by modulation and loader circuits. The compressor is driven by belts or a clutch.
Where this code shows
Press the alarm key or open the Alarms menu on the controller display to list active alarms.
What do these codes mean?
Thermo King codes HP to 531 are all about the refrigeration pressures, scroll compressor limits, modulation and drive. The most common failure type is real condition (5 of 23); 5 need an immediate stop. Start with this check: clean the condenser coil and check the fan runs at the right speed.
How urgent are they?
5 of 23 codes here mean stop now; 16 can wait until the shift ends, but find the cause before the next one; 2 are information only.
- Stop now5
- Check soon16
- Info2
What should I check first?
Clean the condenser coil and check the fan runs at the right speed
Shared checks23 of 23
Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet
Thermo King HPHigh discharge pressure
The discharge pressure is above the limit. The unit may stop to protect the compressor.· Shorted highShorted highStop nowCauses
- Condenser coil dirty
- Condenser fan not running
Checks
- 1Clean the condenser coil
- 2Check the condenser fan operation
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Thermo King LPLow suction pressure
The suction pressure is below the lower limit. The unit may stop to protect the compressor.· OtherOtherStop nowCauses
- Low refrigerant charge
- Restriction in the liquid line
Checks
- 1Check the refrigerant charge
- 2Check the filter drier and expansion valve
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King PSEHigh pressure sensor fault
The high pressure sensor is faulty, so the controller cannot read the discharge pressure reliably.· Real conditionReal conditionStop nowCauses
- Sensor wire damaged
- Sensor failed
Checks
- 1Check the sensor plug and wiring
- 2Compare the reading with a gauge
The reading against the band the controller allows. Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good: If the gauge agrees with the display, fix the machine, not the sensor.
Thermo King 10High discharge pressure or temperature
Compressor discharge pressure or temperature went above the limit the controller allows. Continued running risks damaging the compressor and blowing the high pressure cutout.· Shorted highShorted highStop nowCauses
- Condenser coil blocked with dirt, leaves or bugs
- Condenser fan or fan belt not turning properly
- Overcharge or air or non-condensables in the system
- Receiver or liquid line restricted
Checks
- 1Look at the condenser coil face and clean it if it is plugged
- 2Check the condenser fan runs at the right speed and the shroud is intact
- 3Fit gauges and read discharge pressure against ambient temperature
- 4Look for a hot liquid line before the filter drier showing a restriction
- 5Check the high pressure cutout switch and its wiring separately
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.
Good: Open circuit (OL) between them. Any low reading is the short.
Thermo King 34Check modulation circuit
The controller found a fault in the suction modulation valve circuit, which regulates compressor capacity.· OtherOtherCheck soonCauses
- Modulation valve coil open or shorted
- Harness plug loose
- Valve mechanically stuck
Checks
- 1Measure the modulation valve coil resistance with the plug off
- 2Check drive voltage at the valve plug when commanded
- 3Inspect the plug for corrosion or backed-out pins
- 4Check the modulation valve stem moves freely and is not stuck with dirt or ice
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 48Check belts or clutch
The controller found the compressor drive belt or clutch is not driving as it should, based on speed and pressure behaviour.· OtherOtherCheck soonCauses
- Compressor belt slack or broken
- Clutch coil failed or slipping
- Compressor seized
Checks
- 1Inspect and tension the belts to the manual setting
- 2Check the clutch coil voltage and confirm the clutch actually engages when called
- 3Turn the compressor by hand to feel whether it is free or seized
- 4Check the belt pulleys are in line and not worn, which makes belts slip
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 86Check discharge pressure sensor
The compressor discharge pressure transducer signal is outside its valid range, so the controller cannot see high side pressure.· OtherOtherCheck soonCauses
- Transducer plug corroded or loose
- Wiring to the transducer open or shorted
- Transducer failed
- Missing 5 V reference from the controller
Checks
- 1Check the transducer plug for corrosion and tug each wire
- 2Measure the 5 V reference at the transducer plug
- 3Check the signal voltage against a gauge reading, about 0.5 to 4.5 V over range
- 4Inspect the wiring for open circuits or shorts
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 87Check suction pressure sensor
The compressor suction pressure transducer signal is outside its valid range, so the controller cannot see low side pressure.· OtherOtherCheck soonCauses
- Suction transducer connector damaged
- Open or shorted wire to the controller
- Transducer failed
- 5 V reference missing
Checks
- 1Check the suction transducer plug and its pins
- 2Measure the 5 V supply at the suction transducer plug with the key on
- 3Compare the signal with a manifold gauge reading
- 4Check the wires for continuity and shorts to ground
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 93Low compressor suction pressure
The compressor suction pressure fell below the low limit, which means too little refrigerant is returning to the compressor.· OtherOtherCheck soonCauses
- Low refrigerant charge
- Expansion valve stuck closed or restricted
- Filter drier or liquid line blocked
- Evaporator iced or fan not moving air
Checks
- 1Check the sight glass for bubbles or empty glass
- 2Feel the drier for a temperature drop across it
- 3Run a defrost and check evaporator fan operation
- 4Check the expansion valve bulb is tight on the suction line and insulated
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 94Check loader 1 circuit
The controller found a fault in the output that drives compressor loader 1, which unloads a bank of cylinders to reduce capacity.· OtherOtherCheck soonCauses
- Loader solenoid coil open or burnt
- Plug corroded
- Harness damage near the compressor
Checks
- 1Measure the loader 1 coil resistance with the plug off
- 2Check for supply voltage at the loader 1 plug when the controller commands unloading
- 3Inspect the loader 1 harness and plug for chafing and corrosion
- 4Listen or feel for the loader solenoid click when the controller cycles it
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 95Check loader 2 circuit
The controller found a fault in the output that drives compressor loader 2, a second capacity-control solenoid on the compressor.· OtherOtherCheck soonCauses
- Loader 2 solenoid coil open or burnt
- Plug corroded
- Wiring chafed or shorted
Checks
- 1Measure the loader 2 coil resistance with the plug off
- 2Check for supply voltage at the loader 2 plug when the controller commands unloading
- 3Inspect the loader 2 wiring for chafing near the compressor head
- 4Compare loader 2 coil readings with loader 1 to see which coil is off
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 99High compressor pressure ratio
The ratio of discharge to suction pressure is higher than the compressor should run at, a sign of a restriction or high condensing pressure.· Real conditionReal conditionCheck soonCauses
- Dirty condenser raising discharge pressure
- Low suction from a restriction
- Overcharge or air in the system
Checks
- 1Clean the condenser coil and check the condenser fan is running at the right speed
- 2Compare discharge and suction pressures with the normal chart
- 3Check for restrictions at the drier and expansion valve
- 4Check the refrigerant charge against the sight glass and the pressures
The reading against the band the controller allows. Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good: If the gauge agrees with the display, fix the machine, not the sensor.
Thermo King 115Check high pressure cutout switch
The high pressure cutout switch is open when it should not be, or its circuit has a fault. This switch protects the system from excess discharge pressure.· Real conditionReal conditionStop nowCauses
- High pressure cutout switch tripped for real
- Switch failed open
- Wiring open
Checks
- 1Check discharge pressure and the condenser for a real high pressure cause
- 2Check the switch continuity at rest, when pressure is low, to see if it is open
- 3Inspect the switch wires and plug for breaks and corrosion
- 4Replace the switch if it is open at low pressure
The reading against the band the controller allows. Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good: If the gauge agrees with the display, fix the machine, not the sensor.
Thermo King 116High pressure cut-in switch check
The high pressure cut-in switch, which allows the unit to restart after a high pressure cutout, does not report as expected.· Real conditionReal conditionInfoCauses
- Switch wiring damaged
- Switch failed
Checks
- 1Check the switch and its wiring
- 2Compare with the cutout switch state
The reading against the band the controller allows. Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good: If the gauge agrees with the display, fix the machine, not the sensor.
Thermo King 154Low suction pressure switch failure
The low suction pressure switch circuit does not behave as expected, for example it reads open when the pressure is normal.· OtherOtherCheck soonCauses
- Switch failed or stuck
- Wire open or shorted to the controller
- Connector corroded
Checks
- 1Check the switch state against a gauge reading taken at the same time
- 2Test the switch continuity with pressure applied and removed
- 3Inspect the wiring to the controller input for breaks
- 4Replace the switch if it does not follow the pressure
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 180TriPac compressor alarm
An alarm from the TriPac auxiliary power unit compressor. The cab air conditioning may not work.· OtherOtherCheck soonCauses
- Compressor drive belt or clutch problem
- Refrigerant shortage
Checks
- 1Check the belt and clutch of the compressor
- 2Check the refrigerant pressures
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 507Digital scroll output circuit check (scroll only)
The output that drives the digital scroll compressor unloader is out of range. Capacity control may be coarse.· OtherOtherInfoCauses
- Unloader solenoid coil failed
- Wiring damaged
Checks
- 1Measure the unloader coil resistance
- 2Check the wiring and connector
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 512High compressor suction pressure (scroll only)
The suction pressure of the scroll compressor is above its limit. The unit may run at reduced capacity or shut down the compressor.· OtherOtherCheck soonCauses
- Too much refrigerant or a warm load
- Suction valve or expansion valve fault
Checks
- 1Read the suction pressure on the display against the box temperature
- 2Check the expansion valve operation
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 513Low compressor suction ratio (scroll only)
The pressure ratio across the scroll compressor is below its minimum. This can mean the compressor is not pumping correctly.· Lost messageLost messageCheck soonCauses
- Worn scroll compressor
- Refrigerant shortage
Checks
- 1Read discharge and suction pressures and compute the ratio
- 2Check the refrigerant charge
Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end. Meter test
Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.
Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.
Thermo King 514Low compressor discharge pressure (scroll only)
The discharge pressure of the scroll compressor is lower than the controller expects. Capacity falls and the unit may shut down.· OtherOtherCheck soonCauses
- Low refrigerant charge
- Condenser fan running too fast
Checks
- 1Check the refrigerant charge and the discharge pressure sensor
- 2Check the condenser fan and head pressure control
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 515Minimum ETV discharge superheat temperature (scroll)
The discharge superheat is at the minimum the electronic throttling valve allows. Liquid may be returning to the compressor.· OtherOtherCheck soonCauses
- Expansion valve overfeeding
- Wrong sensor reading
Checks
- 1Compare discharge temperature and pressure for superheat
- 2Check the expansion valve and sensors
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 530Low pressure differential (scroll only)
The pressure difference across the compressor is too low for a scroll to run safely. The controller may stop the compressor.· Real conditionReal conditionCheck soonCauses
- Compressor worn or bypassing
- Refrigerant leak
Checks
- 1Compare suction and discharge pressures with the display
- 2Check the refrigerant charge
The reading against the band the controller allows. Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good: If the gauge agrees with the display, fix the machine, not the sensor.
Thermo King 531Economizer pressure sensor check (scroll only)
The economizer pressure sensor gives an out-of-range signal. The controller cannot regulate the economizer circuit correctly.· OtherOtherCheck soonCauses
- Sensor wiring damaged
- Sensor failed
Checks
- 1Check the sensor connector and supply voltage
- 2Compare the sensor with a gauge reading
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Shared checks
Checks, in order
- 1Clean the condenser coil and check the fan runs at the right speed
- 2Read the suction pressure on the display and compare it with a gauge on the suction service port
- 3Read suction and discharge pressure and compute the ratio, then compare with the alarm
- 4Measure the solenoid coil resistance at the plug with the unit off
- 5Check the drive belt tension and its condition for glazing
- 6Compare the pressure on the display with a manifold gauge on the discharge port
- 7Check the evaporator coil for ice and the fans for rotation
Causes
- Condenser coil blocked with dirt or debris
- Refrigerant leak and a low charge
- Low or high refrigerant charge
- Modulation solenoid failed
Most common here: real condition (5 of 23)
Check the real value with a separate gauge or thermometer before blaming the sensor.
When to stop
You'll notice: A high pressure alarm and, in the worst case, a shutdown; cooling stops until the pressure falls and the switch cuts in again.
Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.
Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.
Sources
Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.