Thermo King · Pressure switches (SR-2/SR-3/SR-4)

Thermo King Fault Code 115

Check high pressure cutout switch

What does Thermo King code 115 mean?

The high pressure cutout switch is open when it should not be, or its circuit has a fault. This switch protects the system from excess discharge pressure. Urgency: stop now - shut down and fix before working on. Check first: check discharge pressure and the condenser for a real high pressure cause.

FaultStop115Thermo King · Pressure switches (SR-2/SR-3/SR-4)

Can I keep running with it?

Stop now

Shut down and fix before working on. Running on risks damage or the machine locks out.

What should I check first?

Check discharge pressure and the condenser for a real high pressure cause

Then 3 more checks
Code shows hereFAULT115

Where this code shows

Press the alarm key or open the Alarms menu on the controller display to list active alarms.

Checks

0 of 4 done

Causes

  • High pressure cutout switch tripped for real
  • Switch failed open
  • Wiring open

How it failed

You'll notice: Alarm 115; the compressor or unit will not run because the safety is open.

Real conditionRead from how the source describes the code

The sensor reading is valid but outside the allowed range - the problem may be real.

allowed rangetime
The reading against the band the controller allows.
Meter test
Check the real value with a separate gauge or thermometer before blaming the sensor.
Good result
If the gauge agrees with the display, fix the machine, not the sensor.

When to stop

Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.

Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Same part, other failures: Refrigeration pressures, scroll compressor limits, modulation and drive

4 other codes on this part are also real condition (PSE, 99, 116, 530). When they show together, start at the wiring and connector they share.

Show the other 14 codes
All 23 Refrigeration pressures, scroll compressor limits, modulation and drive codes on one page

Source

Thermo King Alarm Codes - North America (thermoking.com alarm code list)

This source lists 115 and its meaning. The guidance on this page is general, not taken from it.

The source covers: Thermo King SR-2, SR-3, SR-4 truck and trailer units and related Thermo King controllers (the families the source lists).

Checks, causes, the drawing and the meter test are general workshop guidance, not the maker's procedure. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.