Thermo King · Refrigeration system (SR-2/SR-3/SR-4)

Thermo King Refrigeration pressures, scroll compressor limits, modulation and drive fault codes

This page covers the refrigeration circuit pressures and limits: high-side pressure and cutout, suction-side pressure, the scroll compressor operating limits, capacity modulation and the compressor drive belts and clutch. The discharge side of the refrigeration circuit is watched by a pressure sensor and a high pressure cutout switch.

More about these parts

A suction pressure sensor and a low pressure switch watch the low side of the circuit. On units with a scroll compressor the controller watches the suction pressure, discharge pressure, pressure ratio and discharge superheat, and the economizer pressure. The compressor capacity is adjusted by modulation and loader circuits. The compressor is driven by belts or a clutch.

FaultStop10Thermo King · Refrigeration pressures, scroll compressor limits, modulation and drive
Code shows hereFAULT10

Where this code shows

Press the alarm key or open the Alarms menu on the controller display to list active alarms.

What do these codes mean?

Thermo King codes HP to 531 are all about the refrigeration pressures, scroll compressor limits, modulation and drive. The most common failure type is real condition (5 of 23); 5 need an immediate stop. Start with this check: clean the condenser coil and check the fan runs at the right speed.

How urgent are they?

5 of 23 codes here mean stop now; 16 can wait until the shift ends, but find the cause before the next one; 2 are information only.

  • Stop now5
  • Check soon16
  • Info2

What should I check first?

Clean the condenser coil and check the fan runs at the right speed

Shared checks

23 of 23

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Thermo King HPHigh discharge pressure

    The discharge pressure is above the limit.· Shorted high
    Stop now

    Causes

    • Condenser coil dirty
    • Condenser fan not running

    Checks

    1. 1Clean the condenser coil
    2. 2Check the condenser fan operation
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

    Good: Open circuit (OL) between them. Any low reading is the short.

  • Thermo King LPLow suction pressure

    The suction pressure is below the lower limit.· Other
    Stop now

    Causes

    • Low refrigerant charge
    • Restriction in the liquid line

    Checks

    1. 1Check the refrigerant charge
    2. 2Check the filter drier and expansion valve
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King PSEHigh pressure sensor fault

    The high pressure sensor is faulty, so the controller cannot read the discharge pressure reliably.· Real condition
    Stop now

    Causes

    • Sensor wire damaged
    • Sensor failed

    Checks

    1. 1Check the sensor plug and wiring
    2. 2Compare the reading with a gauge
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 10High discharge pressure or temperature

    Compressor discharge pressure or temperature went above the limit the controller allows.· Shorted high
    Stop now

    Causes

    • Condenser coil blocked with dirt, leaves or bugs
    • Condenser fan or fan belt not turning properly
    • Overcharge or air or non-condensables in the system
    • Receiver or liquid line restricted

    Checks

    1. 1Look at the condenser coil face and clean it if it is plugged
    2. 2Check the condenser fan runs at the right speed and the shroud is intact
    3. 3Fit gauges and read discharge pressure against ambient temperature
    4. 4Look for a hot liquid line before the filter drier showing a restriction
    5. 5Check the high pressure cutout switch and its wiring separately
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Key off, unplug the sensor and the controller. Measure resistance from the signal wire to the supply wire and to battery positive.

    Good: Open circuit (OL) between them. Any low reading is the short.

  • Thermo King 34Check modulation circuit

    The controller found a fault in the suction modulation valve circuit, which regulates compressor capacity.· Other
    Check soon

    Causes

    • Modulation valve coil open or shorted
    • Harness plug loose
    • Valve mechanically stuck

    Checks

    1. 1Measure the modulation valve coil resistance with the plug off
    2. 2Check drive voltage at the valve plug when commanded
    3. 3Inspect the plug for corrosion or backed-out pins
    4. 4Check the modulation valve stem moves freely and is not stuck with dirt or ice
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 48Check belts or clutch

    The controller found the compressor drive belt or clutch is not driving as it should, based on speed and pressure behaviour.· Other
    Check soon

    Causes

    • Compressor belt slack or broken
    • Clutch coil failed or slipping
    • Compressor seized

    Checks

    1. 1Inspect and tension the belts to the manual setting
    2. 2Check the clutch coil voltage and confirm the clutch actually engages when called
    3. 3Turn the compressor by hand to feel whether it is free or seized
    4. 4Check the belt pulleys are in line and not worn, which makes belts slip
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 86Check discharge pressure sensor

    The compressor discharge pressure transducer signal is outside its valid range, so the controller cannot see high side pressure.· Other
    Check soon

    Causes

    • Transducer plug corroded or loose
    • Wiring to the transducer open or shorted
    • Transducer failed
    • Missing 5 V reference from the controller

    Checks

    1. 1Check the transducer plug for corrosion and tug each wire
    2. 2Measure the 5 V reference at the transducer plug
    3. 3Check the signal voltage against a gauge reading, about 0.5 to 4.5 V over range
    4. 4Inspect the wiring for open circuits or shorts
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 87Check suction pressure sensor

    The compressor suction pressure transducer signal is outside its valid range, so the controller cannot see low side pressure.· Other
    Check soon

    Causes

    • Suction transducer connector damaged
    • Open or shorted wire to the controller
    • Transducer failed
    • 5 V reference missing

    Checks

    1. 1Check the suction transducer plug and its pins
    2. 2Measure the 5 V supply at the suction transducer plug with the key on
    3. 3Compare the signal with a manifold gauge reading
    4. 4Check the wires for continuity and shorts to ground
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 93Low compressor suction pressure

    The compressor suction pressure fell below the low limit, which means too little refrigerant is returning to the compressor.· Other
    Check soon

    Causes

    • Low refrigerant charge
    • Expansion valve stuck closed or restricted
    • Filter drier or liquid line blocked
    • Evaporator iced or fan not moving air

    Checks

    1. 1Check the sight glass for bubbles or empty glass
    2. 2Feel the drier for a temperature drop across it
    3. 3Run a defrost and check evaporator fan operation
    4. 4Check the expansion valve bulb is tight on the suction line and insulated
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 94Check loader 1 circuit

    The controller found a fault in the output that drives compressor loader 1, which unloads a bank of cylinders to reduce capacity.· Other
    Check soon

    Causes

    • Loader solenoid coil open or burnt
    • Plug corroded
    • Harness damage near the compressor

    Checks

    1. 1Measure the loader 1 coil resistance with the plug off
    2. 2Check for supply voltage at the loader 1 plug when the controller commands unloading
    3. 3Inspect the loader 1 harness and plug for chafing and corrosion
    4. 4Listen or feel for the loader solenoid click when the controller cycles it
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 95Check loader 2 circuit

    The controller found a fault in the output that drives compressor loader 2, a second capacity-control solenoid on the compressor.· Other
    Check soon

    Causes

    • Loader 2 solenoid coil open or burnt
    • Plug corroded
    • Wiring chafed or shorted

    Checks

    1. 1Measure the loader 2 coil resistance with the plug off
    2. 2Check for supply voltage at the loader 2 plug when the controller commands unloading
    3. 3Inspect the loader 2 wiring for chafing near the compressor head
    4. 4Compare loader 2 coil readings with loader 1 to see which coil is off
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 99High compressor pressure ratio

    The ratio of discharge to suction pressure is higher than the compressor should run at, a sign of a restriction or high condensing pressure.· Real condition
    Check soon

    Causes

    • Dirty condenser raising discharge pressure
    • Low suction from a restriction
    • Overcharge or air in the system

    Checks

    1. 1Clean the condenser coil and check the condenser fan is running at the right speed
    2. 2Compare discharge and suction pressures with the normal chart
    3. 3Check for restrictions at the drier and expansion valve
    4. 4Check the refrigerant charge against the sight glass and the pressures
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 115Check high pressure cutout switch

    The high pressure cutout switch is open when it should not be, or its circuit has a fault.· Real condition
    Stop now

    Causes

    • High pressure cutout switch tripped for real
    • Switch failed open
    • Wiring open

    Checks

    1. 1Check discharge pressure and the condenser for a real high pressure cause
    2. 2Check the switch continuity at rest, when pressure is low, to see if it is open
    3. 3Inspect the switch wires and plug for breaks and corrosion
    4. 4Replace the switch if it is open at low pressure
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 116High pressure cut-in switch check

    The high pressure cut-in switch, which allows the unit to restart after a high pressure cutout, does not report as expected.· Real condition
    Info

    Causes

    • Switch wiring damaged
    • Switch failed

    Checks

    1. 1Check the switch and its wiring
    2. 2Compare with the cutout switch state
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 154Low suction pressure switch failure

    The low suction pressure switch circuit does not behave as expected, for example it reads open when the pressure is normal.· Other
    Check soon

    Causes

    • Switch failed or stuck
    • Wire open or shorted to the controller
    • Connector corroded

    Checks

    1. 1Check the switch state against a gauge reading taken at the same time
    2. 2Test the switch continuity with pressure applied and removed
    3. 3Inspect the wiring to the controller input for breaks
    4. 4Replace the switch if it does not follow the pressure
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 180TriPac compressor alarm

    An alarm from the TriPac auxiliary power unit compressor.· Other
    Check soon

    Causes

    • Compressor drive belt or clutch problem
    • Refrigerant shortage

    Checks

    1. 1Check the belt and clutch of the compressor
    2. 2Check the refrigerant pressures
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 507Digital scroll output circuit check (scroll only)

    The output that drives the digital scroll compressor unloader is out of range.· Other
    Info

    Causes

    • Unloader solenoid coil failed
    • Wiring damaged

    Checks

    1. 1Measure the unloader coil resistance
    2. 2Check the wiring and connector
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 512High compressor suction pressure (scroll only)

    The suction pressure of the scroll compressor is above its limit.· Other
    Check soon

    Causes

    • Too much refrigerant or a warm load
    • Suction valve or expansion valve fault

    Checks

    1. 1Read the suction pressure on the display against the box temperature
    2. 2Check the expansion valve operation
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 513Low compressor suction ratio (scroll only)

    The pressure ratio across the scroll compressor is below its minimum.· Lost message
    Check soon

    Causes

    • Worn scroll compressor
    • Refrigerant shortage

    Checks

    1. 1Read discharge and suction pressures and compute the ratio
    2. 2Check the refrigerant charge
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 514Low compressor discharge pressure (scroll only)

    The discharge pressure of the scroll compressor is lower than the controller expects.· Other
    Check soon

    Causes

    • Low refrigerant charge
    • Condenser fan running too fast

    Checks

    1. 1Check the refrigerant charge and the discharge pressure sensor
    2. 2Check the condenser fan and head pressure control
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 515Minimum ETV discharge superheat temperature (scroll)

    The discharge superheat is at the minimum the electronic throttling valve allows.· Other
    Check soon

    Causes

    • Expansion valve overfeeding
    • Wrong sensor reading

    Checks

    1. 1Compare discharge temperature and pressure for superheat
    2. 2Check the expansion valve and sensors
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 530Low pressure differential (scroll only)

    The pressure difference across the compressor is too low for a scroll to run safely.· Real condition
    Check soon

    Causes

    • Compressor worn or bypassing
    • Refrigerant leak

    Checks

    1. 1Compare suction and discharge pressures with the display
    2. 2Check the refrigerant charge
    allowed rangetime
    The reading against the band the controller allows.

    Meter test

    Check the real value with a separate gauge or thermometer before blaming the sensor.

    Good: If the gauge agrees with the display, fix the machine, not the sensor.

  • Thermo King 531Economizer pressure sensor check (scroll only)

    The economizer pressure sensor gives an out-of-range signal.· Other
    Check soon

    Causes

    • Sensor wiring damaged
    • Sensor failed

    Checks

    1. 1Check the sensor connector and supply voltage
    2. 2Compare the sensor with a gauge reading
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

Shared checks

Checks, in order

  1. 1Clean the condenser coil and check the fan runs at the right speed
  2. 2Read the suction pressure on the display and compare it with a gauge on the suction service port
  3. 3Read suction and discharge pressure and compute the ratio, then compare with the alarm
  4. 4Measure the solenoid coil resistance at the plug with the unit off
  5. 5Check the drive belt tension and its condition for glazing
  6. 6Compare the pressure on the display with a manifold gauge on the discharge port
  7. 7Check the evaporator coil for ice and the fans for rotation

Causes

  • Condenser coil blocked with dirt or debris
  • Refrigerant leak and a low charge
  • Low or high refrigerant charge
  • Modulation solenoid failed

Most common here: real condition (5 of 23)

Check the real value with a separate gauge or thermometer before blaming the sensor.

When to stop

You'll notice: A high pressure alarm and, in the worst case, a shutdown; cooling stops until the pressure falls and the switch cuts in again.

Tilt, load and interlock cutouts are what keep a lift or telehandler from tipping. Never bypass or bridge one to keep working; get the fault found before anyone goes up or lifts again.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.

Machine down?

Get a replacement machine or a technician - suppliers in the UAE contact you.

Post a request
EquipmentsFinder

Need equipment? Have equipment?

Buyers post one request and get quotes from suppliers. Suppliers list free and reach active demand.