Thermo King · Compressor and valves (SR-2/SR-3/SR-4)
Thermo King Solenoid, expansion and heating valves and cooling and heating cycle checks fault codes
This page covers the valve and drive circuits: liquid, suction and hot gas solenoids, throttling, economizer and expansion valves, heating and water valves, and the cooling and heating cycle checks. Several solenoid valves route refrigerant, such as the hot gas, liquid line, suction line and purge valves.
More about these partsLess
Electronic throttling and expansion valves and the economizer valve meter the refrigerant flow. Heating comes from hot gas, a heater or a coolant water valve. The controller watches whether the box actually cools or heats when it commands cooling or heating.
Where this code shows
Press the alarm key or open the Alarms menu on the controller display to list active alarms.
What do these codes mean?
Thermo King codes 21 to 175 are all about the solenoid, expansion and heating valves and cooling and heating cycle checks. The most common failure type is open circuit (2 of 21); 2 need an immediate stop. Start with this check: measure the coil resistance and compare it with the service data.
How urgent are they?
2 of 21 codes here mean stop now; the other 19 can wait until the shift ends, but find the cause before the next one.
- Stop now2
- Check soon19
What should I check first?
Measure the coil resistance and compare it with the service data
Shared checks21 of 21
Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet
Thermo King 21Cooling cycle check
During cooling the controller sees the temperatures and pressures behave in a way that does not match a working cooling cycle, so it flags the cycle for inspection.· OtherOtherCheck soonCauses
- Low refrigerant charge
- Restricted filter drier or liquid line
- Weak compressor valves
Checks
- 1Compare return and discharge air temperatures to see the temperature split
- 2Check sight glass and pressures against the normal range
- 3Feel across the filter drier for a temperature drop that marks a restriction
- 4Check the expansion valve bulb is clamped tightly on the suction line
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 22Heating cycle check
During heating or defrost the controller sees the box or coil not warming the way a working heat cycle should, so it flags the heating cycle for inspection.· OtherOtherCheck soonCauses
- Hot gas solenoid not opening
- Low refrigerant charge or poor compressor output
- Heat or defrost damper stuck
Checks
- 1Command heat and feel whether the hot gas line gets hot
- 2Check the hot gas solenoid coil for voltage and a click when energised
- 3Look at the damper linkage for freedom of movement
- 4Verify the return air sensor reading against a thermometer
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 23Cooling cycle fault
The cooling cycle has failed its check outright: the unit is running in cool but not removing heat. This is the harder version of the cooling cycle check alarm.· OtherOtherStop nowCauses
- Refrigerant lost through a leak
- Compressor damaged or not pumping
- Liquid line solenoid stuck closed
- Drive belt or clutch slipping
Checks
- 1Fit gauges and note low suction with high superheat or no pressure difference
- 2Check the compressor belt or clutch is driving the compressor
- 3Test the liquid line solenoid coil and valve movement
- 4Leak check the system and look for oil traces at joints
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 24Heating cycle fault
The heating cycle has failed its check: the unit is told to heat but the box and coil are not warming. It is the failed version of the heating cycle check.· OtherOtherStop nowCauses
- Hot gas valve stuck shut or its coil open
- Electric heat element or contactor failed
- Compressor not producing hot gas
Checks
- 1Test whether the hot gas line warms up when heat is requested
- 2Check electric heaters for current draw and the contactor for pull-in
- 3Check the hot gas solenoid coil resistance with the plug off
- 4Inspect the heat damper linkage and door for free movement and ice build-up
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 26Check refrigeration capacity
The unit is not removing heat as fast as it should for the conditions: the pulldown is too slow or the temperature split across the coil is too small.· OtherOtherCheck soonCauses
- Dirty condenser coil
- Low charge or a restricted drier
- Worn compressor
- Evaporator iced or airflow blocked by load
Checks
- 1Check both coils for dirt or ice and clean as needed
- 2Measure air temperature difference across the evaporator
- 3Read suction and discharge pressure and compare to the normal range
- 4Check the load is not blocking the return air
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 32Refrigeration capacity low
The unit has been running a while and measured capacity is below the expected level, so the controller reports low refrigeration capacity.· OtherOtherCheck soonCauses
- Dirty condenser or evaporator coil
- Low refrigerant
- Compressor wear
- Economizer or liquid solenoid not operating
Checks
- 1Inspect and clean the condenser and evaporator coils
- 2Check the refrigerant charge via the sight glass
- 3Compare gauge pressures to the normal chart at current ambient
- 4Verify the liquid line and economizer solenoids open
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 39Check water valve circuit
A fault was found in the water valve circuit, used on units with a coolant heat valve to heat the box or defrost with engine coolant.· OtherOtherCheck soonCauses
- Water valve coil open
- Wiring to the valve damaged
- Valve stuck by corrosion
Checks
- 1Measure the valve coil resistance with the plug off
- 2Check voltage at the valve plug when heat is commanded
- 3Look for coolant flow through the valve when open
- 4Check the harness to the water valve for damage along its route near the engine
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 45Check hot gas circuit
The controller detects a problem in the hot gas or hot gas bypass valve circuit used for heating and defrost.· OtherOtherCheck soonCauses
- Hot gas solenoid coil open
- Plug loose or corroded
- Valve stuck
Checks
- 1Measure the solenoid coil resistance with the plug off
- 2Check voltage at the plug when heat or defrost is commanded
- 3Feel the hot gas line during defrost for warmth
- 4Inspect the harness to the hot gas valve for chafing against the compressor
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 52Check heat circuit
The controller found a fault in the heat circuit, the output that controls heating components such as the heat valve or heaters.· OtherOtherCheck soonCauses
- Heater contactor failed
- Heater element open
- Wiring fault
Checks
- 1Check the heater contactor pull-in when heat is called
- 2Measure the electric heater element resistance and compare the three elements
- 3Look at the heater wiring and lugs for burn marks or loose connections
- 4Check the heat circuit fuses and breakers for a blown or tripped one
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 53Check economizer valve circuit
The economizer valve circuit shows a fault. The economizer boosts capacity at low box temperatures, so capacity will be lower.· OtherOtherCheck soonCauses
- Economizer solenoid coil open
- Plug corrosion
- Valve jammed
Checks
- 1Measure the economizer solenoid coil resistance
- 2Check for supply voltage at the economizer coil when the controller commands it open
- 3Check the economizer valve for mechanical sticking by tapping it with the coil energised
- 4Inspect the harness at the compressor for heat damage or chafing
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 67Check liquid line solenoid circuit
The controller found a fault in the liquid line solenoid circuit. This valve opens to let liquid refrigerant flow to the expansion valve whenever the unit cools.· OtherOtherCheck soonCauses
- Solenoid coil open or burnt
- Plug at the valve corroded
- Harness chafed near the receiver
Checks
- 1Measure the solenoid coil resistance with the plug off
- 2Check for supply voltage at the plug when cooling is commanded
- 3Listen or feel for the valve click on and off
- 4Inspect the harness near the receiver for rubbing
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 89Check electronic throttling valve (ETV) circuit
The controller found a fault in the circuit that drives the electronic throttling valve (ETV), which meters suction gas to control capacity and protect the engine.· OtherOtherCheck soonCauses
- ETV stepper coil open or shorted
- Connector at the valve loose or corroded
- Harness damaged near the compressor
- Valve stuck
Checks
- 1Measure the ETV coil resistance on each winding
- 2Check the plug pins for corrosion and backed-out terminals
- 3Inspect the harness near the compressor for heat or chafe damage
- 4Run an ETV test in the controller menu and watch the valve move
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 105Receiver tank pressure solenoid circuit check
The circuit for the receiver tank pressure solenoid is open or shorted. The controller cannot hold the receiver pressure steady.· OtherOtherCheck soonCauses
- Solenoid coil open or shorted
- Wiring chafed near the tank
Checks
- 1Measure the coil resistance at the plug
- 2Check the wiring and connector at the solenoid
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 106Purge valve circuit check
The purge valve circuit is open or shorted. The controller cannot clear refrigerant or oil from the line through the purge valve.· Open circuitOpen circuitCheck soonCauses
- Purge valve coil failed
- Wiring damaged
Checks
- 1Measure the coil resistance
- 2Check the connector for water and the wires for chafing
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Thermo King 107Condenser inlet solenoid circuit check
The circuit of the condenser inlet solenoid is open or shorted. The valve cannot be switched as the controller commands, which affects head pressure control.· OtherOtherCheck soonCauses
- Coil failed
- Plug corroded
Checks
- 1Measure the coil resistance and check for a short to ground
- 2Inspect the plug and wiring
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 110Suction line solenoid circuit check (zone)
The circuit of the suction line solenoid for a zone is open or shorted. Multi-temp units can lose control of that zone.· Lost messageLost messageCheck soonCauses
- Solenoid coil failed
- Wire chafed or cut
Checks
- 1Measure the coil resistance
- 2Check the wiring and connector at the valve
Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end. Meter test
Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.
Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.
Thermo King 113Check electric heat circuit
The controller found a fault in the electric heat circuit, the output that powers the resistance heaters on units fitted with them for heating and defrost.· OtherOtherCheck soonCauses
- Heater element burnt open
- Heater contactor not pulling in
- Overtemperature switch open
Checks
- 1Measure each electric heater element resistance and compare the elements
- 2Check the heater contactor pulls in when heat is requested
- 3Check the heater overtemperature switch is closed at normal temperature
- 4Inspect the heater wiring and lugs for burnt insulation
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 121PWM liquid injection circuit check
The pulse-width liquid injection valve circuit is open or shorted. The controller cannot cool the compressor with injected liquid.· Open circuitOpen circuitCheck soonCauses
- Coil failed
- Wiring damaged
Checks
- 1Measure the coil resistance
- 2Check the wiring and connector
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
Good: Near 0 Ω on each wire. The part reads its listed resistance, not OL.
Thermo King 142Check Thermax valve
The controller found a fault in the Thermax valve circuit, the valve that regulates refrigerant or coolant flow for heating on units fitted with it.· OtherOtherCheck soonCauses
- Valve coil open or shorted
- Connector at the valve corroded
- Valve body stuck from debris
Checks
- 1Measure the Thermax valve coil resistance with the plug off and compare the winding
- 2Check for supply voltage at the valve plug when heat is commanded
- 3Inspect the connector for green corrosion and spread pins
- 4Run the output test from the controller and listen for the valve to move
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Thermo King 156Suction and liquid heat exchanger bypass valve check
The bypass valve of the suction and liquid heat exchanger is not responding as the controller commands. Superheat and capacity control are affected.· Part or controllerPart or controllerCheck soonCauses
- Valve coil open or shorted
- Plug corroded
Checks
- 1Measure the coil resistance
- 2Check the wiring and connector
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Check power and ground at the module connector with the key on, then its fuses.
Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.
Thermo King 175Electronic expansion valve check (CR)
The electronic expansion valve of a CR unit does not respond as commanded. The controller cannot regulate the refrigerant flow into the coil.· OtherOtherCheck soonCauses
- Expansion valve coil open or shorted
- Wiring damaged
Checks
- 1Measure the valve coil resistance
- 2Check the plug and wiring
Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins. Meter test
Read the code with the service tool and note which other codes are active with it.
Good: Codes that appear together usually share one cause - start with the wiring they share.
Shared checks
Checks, in order
- 1Measure the coil resistance and compare it with the service data
- 2Measure the valve coil resistance at the plug with the unit off
- 3Check the heat valve circuit with a meter for supply and ground
- 4Run a pretrip test and watch which step fails
- 5Check the wiring and plug for corrosion and chafing
- 6Check the plug and wiring for damage and green corrosion
- 7Measure the heater element resistance with the unit off
Causes
- Solenoid coil open or shorted
- Valve coil open or shorted
- Valve or heater element failed
- Refrigerant shortage or restriction
Most common here: open circuit (2 of 21)
Key off, unplug both ends. Measure each wire end to end, then the part itself across its pins.
When to stop
You'll notice: Cooling or heating is reduced or lost, with the alarm number on the display.
Lower attachments to the ground and relieve hydraulic pressure before loosening any fitting. Never feel for a leak with your hand - oil under pressure can inject through skin.
Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.
Sources
Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.