Generator size calculator (kVA)

Work out the generator kVA you need from the total running load, the largest motor and the way that motor starts. The result adds spare capacity and rounds up to a standard generator size.

The formula

kVA = (running kW ÷ PF + motor start extra) × (1 + spare %).

What it works out

The generator kVA a site load needs.

Why it matters

Hire a generator that starts the motors and does not overload.

How to use it

  1. Enter the Total Running Load in kW: the sum of everything that runs at the same time, taken from nameplates or the load schedule.
  2. Enter the Largest Motor in kW. This is the one that causes the biggest starting surge.
  3. Choose Motor Starting: Direct on line (×6), Star-delta (×3), Soft starter (×2.5) or VFD / inverter (×1.5).
  4. Check the Power Factor (0.8 is standard for generators) and set the Spare Capacity as a percentage.
  5. Read the Running kVA, Motor Start Extra and Required kVA, then the Suggested Generator, the next standard size up.

The formula

Running kVA = running kW ÷ power factor. Motor start extra = (start factor − 1) × largest motor kW ÷ power factor. Required kVA = (running kVA + motor start extra) × (1 + spare capacity %). The suggested generator is the smallest standard size that is at least the required kVA.

What changes the result

The way the largest motor starts changes the answer more than most people expect. A motor started direct on line draws about six times its running current, a star-delta starter about three, a soft starter about two and a half and a variable frequency drive about one and a half. A soft starter or VFD can bring the required size down by a full step. Spare capacity covers future load and keeps the generator from running flat out, and a generator also loses output in high ambient temperature, so do not set the margin to 0.

Sizing on UAE sites

Site generators in the UAE are normally rated in kVA at a power factor of 0.8, three-phase 400 V, and prime or standby ratings differ, so ask which rating a quoted size refers to. Summer heat reduces output, and cranes, pumps and compressors with large motors are the loads that overload an undersized set. This calculator gives an estimate for planning; have an electrician or the generator supplier confirm the final size against your load schedule.

Worked examples

  • A site with a 120 kW running load and a 30 kW star-delta motor needs 281.3 kVA after a 25% margin, so look for a 300 kVA generator.
  • Start the same 30 kW motor direct on line and the start extra grows to 187.5 kVA, which lifts the requirement to 421.9 kVA and the suggestion to 500 kVA.
  • Fit a VFD to that motor and the start extra drops to 18.75 kVA, so the required size is 210.9 kVA.
  • A small site with a 40 kW load and an 11 kW pump has a running load of 50 kVA and needs a 100 kVA set.

Frequently asked questions

What size generator do I need?

Add up the running load in kW, find the largest motor and how it starts, and enter them in the calculator above. The Suggested Generator is the standard kVA size to look for.

How do I convert kW to kVA for a generator?

Divide the kW by the power factor. At the usual 0.8, a load of 80 kW needs 100 kVA before adding motor starting and spare capacity.

Why is motor starting included?

A motor draws several times its running current for a moment when it starts. The generator must carry that surge on top of the rest of the load without the voltage dropping.

How much spare capacity should I add?

The default is 25%, which leaves room for extra load and keeps the set away from full load. Use more if the site will grow or the generator will work in strong heat.

Who confirms the final generator size?

An electrician or the generator supplier. This tool is a planning estimate, and real loads, cable lengths and the generator’s own rating can change the answer.

Add this calculator to your website

Copy the code and paste it into your page. The calculator is free and works as it does here.

<iframe src="https://www.equipmentsfinder.com/embed/field-tools/generator-size-calculator" title="Generator size calculator (kVA)" width="100%" height="620" style="border:0;max-width:720px" loading="lazy"></iframe>
<p style="font-size:12px"><a href="https://www.equipmentsfinder.com/field-tools/generator-size-calculator">Generator size calculator (kVA)</a> by <a href="https://www.equipmentsfinder.com">EquipmentsFinder</a></p>