This page covers communications and configuration: CAN and display links, the radio expansion board, the DAS data logger, configuration and spare inputs, and options and accessories. The controller exchanges data with the display, the expansion module and the I/O controller over CAN or a cable.

More about these parts

The radio expansion board links the controller to the telematics radio. The data logger records temperatures and events. These alarms report an unconfigured unit, a missing setpoint, a profile mismatch or a fault on a spare input or output. These alarms report faults in optional equipment such as the drain hose heater, humidity sensor and fresh air exchange, or an aborted evacuation mode.

FaultCheck144Thermo King · CAN, display, radio, data logger, configuration and options
Code shows hereFAULT144

Where this code shows

Press the alarm key or open the Alarms menu on the controller display to list active alarms.

What do these codes mean?

Thermo King codes - C - to 516 are all about the cAN, display, radio, data logger, configuration and options. The most common failure type is lost message (5 of 24); 2 need an immediate stop. Start with this check: check the CAN wires and plugs for damage and corrosion.

How urgent are they?

2 of 24 codes here mean stop now; 4 can wait until the shift ends, but find the cause before the next one; 18 are information only.

  • Stop now2
  • Check soon4
  • Info18

What should I check first?

Check the CAN wires and plugs for damage and corrosion

Shared checks

24 of 24

Stop nowshut down and fix before working onCheck soonfind the cause before the next shiftInfonothing is failing yet

  • Thermo King - C -Communication failure, microprocessor to in-cab control box

    The link between the unit microprocessor and the in-cab control box is lost.· Other
    Stop now

    Causes

    • Cab cable or plug damaged
    • Control box failed

    Checks

    1. 1Check the cable and plugs from the cab box to the unit
    2. 2Check the box supply
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 111Unit not configured correctly (zone)

    The unit configuration does not match the options the controller sees.· Other
    Info

    Causes

    • Configuration changed or reset
    • Option fitted but not configured

    Checks

    1. 1Check the unit configuration against the fitted options
    2. 2Reload the correct configuration
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 127Setpoint not entered (zone)

    No temperature setpoint has been entered for the zone.· Other
    Check soon

    Causes

    • Setpoint never entered
    • Setpoint lost after a reset

    Checks

    1. 1Enter the required setpoint for the zone
    2. 2Check the controller memory if the setpoint is lost again
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 135Spare digital inputs check

    One of the spare digital inputs on the controller reads a state that is not expected.· Other
    Info

    Causes

    • Spare input wired to an accessory
    • Wiring fault

    Checks

    1. 1Check what is wired to the spare input
    2. 2Check the wire for shorts
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 137Spare digital outputs check

    One of the spare digital outputs on the controller shows a fault.· Other
    Info

    Causes

    • Accessory wired to the output drawing too much
    • Wiring fault

    Checks

    1. 1Check what is connected to the spare output
    2. 2Check the wiring for shorts
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 138Log DAS real time clock battery failure

    The battery that keeps the data logger clock alive has failed.· Lost message
    Info

    Causes

    • Clock battery flat
    • Loose battery connection

    Checks

    1. 1Replace the clock battery
    2. 2Reset the clock after replacing it
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 139Abort evacuation mode

    The evacuation mode, used during service to pull the system down, was aborted before it finished.· Other
    Info

    Causes

    • Mode interrupted by the operator
    • Unit power lost

    Checks

    1. 1Restart the evacuation mode if the service is not complete
    2. 2Check the supply during the procedure
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 143Remote drain hose heater output check (zone)

    The output that powers the drain hose heater of a remote evaporator is faulty.· Other
    Info

    Causes

    • Heater element failed
    • Wiring damaged

    Checks

    1. 1Check the heater and its wiring
    2. 2Measure the heater resistance
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 144Lost CAN communications to expansion module

    The main controller stopped hearing the I/O expansion module on the CAN bus, so the inputs and outputs wired to that module are unavailable.· Lost message
    Check soon

    Causes

    • CAN wiring between the controller and the module cut or chafed
    • Module connector loose or corroded
    • Module not powered because of a blown fuse
    • Module itself failed

    Checks

    1. 1Check the supply and ground to the expansion module with a meter at its plug
    2. 2Inspect the CAN cable between controller and module for chafing and pinched sections
    3. 3Check the module connector for water and corrosion
    4. 4Swap in a known-good module to see whether the alarm follows it
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 146Software version mismatch

    Two controllers or modules on the unit are running software versions that are not compatible, so they cannot cooperate fully.· Part or controller
    Check soon

    Causes

    • One module replaced with a different software revision
    • Software update only partly completed
    • Wrong software file loaded

    Checks

    1. 1Read the software versions of each module from the controller menu
    2. 2Compare them with the revision the manual or service bulletin calls for
    3. 3Reload the correct software with the service tool on the lagging module
    4. 4Clear the alarm and check the versions match after a power cycle
    ControllerPartSupplySignalGround?
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Check power and ground at the module connector with the key on, then its fuses.

    Good: Battery voltage on power, under 0.2 V drop on ground. Then it needs the service tool.

  • Thermo King 152DAS failed sensor

    The data logger has detected a failed sensor input.· Other
    Info

    Causes

    • Sensor wiring damaged
    • Sensor failed

    Checks

    1. 1Check which logger sensor input failed
    2. 2Check the sensor wiring
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 155Lost CAN communications to HMI

    The controller lost communication with the HMI, the display and keypad the operator uses, so the screen may go blank or frozen.· Lost message
    Check soon

    Causes

    • HMI cable or connector damaged
    • Supply voltage to the HMI missing
    • CAN wires open or shorted
    • HMI failed

    Checks

    1. 1Check the cable between the controller and HMI for cuts and pinched sections
    2. 2Measure the supply and ground at the HMI connector with a meter
    3. 3Reseat the HMI connectors and look closely for bent or pushed-back pins
    4. 4Try a known-good HMI to see if the display recovers
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 157OptiSet Plus profile mismatch

    The OptiSet Plus load profile stored in the controller does not match what the unit expects.· Other
    Info

    Causes

    • Profile loaded for another unit
    • Controller memory changed

    Checks

    1. 1Reload the correct OptiSet Plus profile
    2. 2Check the profile settings
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 160Lost CAN communications to radio expansion board

    The controller lost its link to the radio expansion board.· Lost message
    Info

    Causes

    • CAN wire damaged
    • Board failed

    Checks

    1. 1Check the CAN wiring and plug of the board
    2. 2Check the board supply
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 161Log DAS real time clock invalid

    The real time clock of the data logger holds an invalid time.· Other
    Info

    Causes

    • Clock battery flat
    • Clock never set

    Checks

    1. 1Set the logger clock
    2. 2Check the clock battery
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 188Log DAS microprocessor fault

    The data logger microprocessor reports a fault.· Other
    Info

    Causes

    • Logger internal fault
    • Supply voltage dip

    Checks

    1. 1Cycle the unit power and recheck
    2. 2Replace the logger if it returns
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 216Check DAS digital inputs

    One of the digital inputs of the data logger is in an unexpected state.· Lost message
    Info

    Causes

    • Input wiring fault
    • Switch fault

    Checks

    1. 1Check the wiring to the logger inputs
    2. 2Check the switch that feeds the input
    Module AModule BCAN HCAN L120 Ω120 Ω
    Typical J1939 link: two modules, CAN high and low, a 120 Ω terminator at each end.

    Meter test

    Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

    Good: About 60 Ω on a two-terminator J1939 link. About 120 Ω means one terminator or one leg is open.

  • Thermo King 233REB switching off, conservative to full null

    The radio expansion board is switching its mode of operation.· Other
    Info

    Causes

    • Normal mode change
    • Power change

    Checks

    1. 1Check whether the board continues to work normally
    2. 2Check its supply
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 234Relative humidity sensor circuit check

    The humidity sensor circuit is out of range.· Other
    Info

    Causes

    • Sensor wire damaged
    • Sensor failed

    Checks

    1. 1Check the sensor plug and wiring
    2. 2Compare the reading with a hand humidity meter
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 250DAS clock time reset

    The data logger clock was reset to a default time.· Other
    Info

    Causes

    • Clock battery flat
    • Power lost to the logger

    Checks

    1. 1Set the logger clock to the correct time
    2. 2Check the logger power and battery
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 251Radio expansion board configuration check

    The radio expansion board is configured wrongly or not as the controller expects.· Other
    Info

    Causes

    • Board replaced and not configured
    • Setting changed

    Checks

    1. 1Check the board configuration
    2. 2Reload the correct settings
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 252Auto fresh air exchange circuit check

    The circuit of the automatic fresh air exchange is faulty.· Other
    Info

    Causes

    • Actuator failed
    • Wiring fault

    Checks

    1. 1Check the actuator movement and wiring
    2. 2Run the vent from the diagnostics menu
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 253REB on back-up battery, alarms disabled

    The radio expansion board is running on its back-up battery, so alarms are disabled.· Other
    Info

    Causes

    • Main supply to the board lost
    • Fuse blown

    Checks

    1. 1Check the main supply and fuse of the board
    2. 2Check the connection
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

  • Thermo King 516I/O controller to application controller communication failure

    The input/output controller and the application controller cannot talk to each other.· Other
    Stop now

    Causes

    • CAN wire damaged
    • Controller power supply problem

    Checks

    1. 1Check the CAN wires and plugs between the controllers
    2. 2Check the controller supply voltage
    ControllerPartSupplySignalGround
    Typical three-wire sensor or two-wire coil. Your wiring diagram has the real pins.

    Meter test

    Read the code with the service tool and note which other codes are active with it.

    Good: Codes that appear together usually share one cause - start with the wiring they share.

Shared checks

Checks, in order

  1. 1Check the CAN wires and plugs for damage and corrosion
  2. 2Check the CAN wiring of the board for damage
  3. 3Set the logger clock to the correct local time
  4. 4Check the unit configuration against the fitted options
  5. 5Check the accessory wiring and plug for damage
  6. 6Check the supply to the display or module with a meter
  7. 7Check the supply and fuse of the board with a meter

Causes

  • CAN wires damaged
  • CAN wire damaged
  • Clock battery flat
  • Configuration lost

Most common here: lost message (5 of 24)

Key off. Measure resistance between CAN high and CAN low at the diagnostic connector.

When to stop

You'll notice: The display or a module stops responding and the alarm number shows on the display.

Let the engine cool before opening the cooling system; a hot cap releases scalding coolant. Running on with an overheat warning risks a head gasket or seized engine.

Each code above shows its own urgency. Call a technician if the checks above do not find the cause, if the code returns after clearing, or if the fix needs a service tool, a calibration or a software update.

Sources

Codes and meanings come from the sources above; short titles shorten the standard J1939 wording. Failure types, checks, meter tests and drawings are general workshop guidance, not the maker's. Codes can differ by serial number and software - confirm with the service manual or your dealer before replacing parts.

Machine down?

Get a replacement machine or a technician - suppliers in the UAE contact you.

Post a request
EquipmentsFinder

Need equipment? Have equipment?

Buyers post one request and get quotes from suppliers. Suppliers list free and reach active demand.